VoCALL Compact 

5 Line Fire Telephone & 

Disabled Refuge System 

 

 

User Manual & Log Book 

 

Site Name 

 

 

Address 

 

 
 
 
 
 
 
 

Contractor 

 

 
 
 
 
 
 
 

Commissioned 

 

 

 

 

 

Summary of Contents for EVCS Compact

Page 1: ...VoCALL Compact 5 Line Fire Telephone Disabled Refuge System User Manual Log Book Site Name Address Contractor Commissioned ...

Page 2: ...ystems are recommended for all public buildings and multi story buildings over four floors by BS5588 Disabled Refuge systems are required in buildings where the public or disabled staff gain access to any floor other than the ground floor using lifts Product Overview A VoCALL EVCS comprises of two functional blocks the master handset and outstations type A type B or Jack points with the quantities...

Page 3: ...the outstation answers the call the green zone LED will go steady and the handset will connect to the called outstation To end the call Hang up receiver or press the Zone key again to place the outstation on HOLD the zone led will flash slowly when held Conference Call Up to five calls can be conference called by answering the calls or dialling the calls as described above the master handset must ...

Page 4: ... supply is unavailable or a fuse has ruptured Maintenance It is a requirement of BS5839pt9 that a maintenance agreement be in place for the EVCS the maintenance schedule should be as follows Weekly Lift a different handset on the system each week and make a call to the control repeat each week until all points are tested record results in the site log Monthly Test one handset on each exchange by l...

Page 5: ...site it is essential all units are on the same mains phase as they are classified TEN 230V powering from different phases can mean a 440V potential can be present in a unit during a major fault incident Anti static handling guidelines Make sure that electro static handling precautions are taken immediately before handling PCBs and other static sensitive components Before handling any static sensit...

Page 6: ...means large currents will flow if they are accidentally short circuited causing burns and a risk of fire exercise caution when handling batteries Power Up Procedure Always apply mains power before connecting batteries do not commission VoCALL Compact on batteries as the high inrush current required by the power supply may rupture the battery fuse Always connect the Positive Red terminal first Powe...

Page 7: ...Commissioning In accordance with Section 4 of BS 5839 Part 9 2002 sub clause 21 2C 1 Intelligible conversation is heard at all locations 2 All controls and indicators operate correctly The system is accepted in good working order and in accordance with BS5839 Part 9 2002 record drawings operating instructions and a system log book have been supplied and received Attention has been drawn to the rec...

Page 8: ...CALL Compact User Guide Log Book Site Specific Information Equipment Locations Master Handset Phone Locations Cable ID Line Area Served 1 2 3 4 5 Document DCC VCC7002 01 Rev 0 September 2008 Page 8 of 12 ...

Page 9: ...VoCALL Compact User Guide Log Book Log Book Page 1 Date Event or Work Done Engineer Company Signature VoCALL System commissioned Document DCC VCC7002 01 Rev 0 September 2008 Page 9 of 12 ...

Page 10: ...VoCALL Compact User Guide Log Book Log Book Page __ Date Event or Work Done Engineer Company Signature Copy this page as many times as required Document DCC VCC7002 01 Rev 0 September 2008 Page 10 of 12 ...

Page 11: ...VoCALL Compact User Guide Log Book Log Book Page __ Date Event or Work Done Engineer Company Signature Copy this page as many times as required Document DCC VCC7002 01 Rev 0 September 2008 Page 11 of 12 ...

Page 12: ...age 12 of 12 Notes The VoCALL Compact EVCS is designed and manufactured in the UK by Current Thinking Ltd Unit 91 Silver Briar Enterprise Park East Sunderland SR5 2TQ United Kingdom Tel 44 0 191 516 6533 Fax 44 0 191 516 6588 Email info current thinking com www current thinking com ...