Storage temperature
- 25° C to + 60° C
Operating Altitude
0 - 1000 m, above 1000 m with derating
Humidity
5% to 95% Relative Humidity
Pollution degree
Pollution Degree 3
Heat Dissipation
During start
4.5 watts per ampere
During run
MCD5-0021B - MCD5-0053B
= 39 watts approx
MCD5-0068B - MCD5-0105B
= 51 watts approx
MCD5-0131B - MCD5-0215B
= 120 watts approx
MCD5-0245C - MCD5-0927C
4.5 watts per ampere approx
MCD5-1200C - MCD5-1600C
4.5 watts per ampere approx
Certification
C
✓
IEC 60947-4-2
UL/ C-UL
UL 508
CE
IEC 60947-4-2
CCC
GB 14048-6
Marine
(MCD5-0021B - MCD5-0215B only)
Lloyds Marine No 1 Specification
RoHS
Compliant with EU Directive 2002/95/EC
10.1 Accessories
10.1.1 LCP Remote Mounting Kit
The MCD 500 LCP can be mounted up to 3 metres away from the soft starter, allowing remote control and monitoring. The
remote LCP also allows parameter settings to be copied between soft starters.
•
175G0096 Control Panel LCP501
10.1.2 Communication Modules
MCD 500 soft starters support network communication using the Profibus, DeviceNet and Modbus RTU protocols, via an
easy-to-install communications module. The communications module plugs directly onto the side of the starter.
•
175G9000 Modbus Module
•
175G9001 Profibus Module
•
175G9002 DeviceNet Module
•
175G9009 MCD USB Module