8-4 User Screen - Bottom Left
Option:
Function:
Selects the item displayed in the bottom left
part of the screen.
Blank
Displays no data in the selected area,
allowing long messages to be shown without
overlapping.
Starter State
The starter's operating state (starting,
running, stopping or tripped). Only available
for “Top L” and “Btm L”.
Motor Current
The average current measured on three
phases.
Motor pf
The motor's power factor, measured by the
soft starter.
Mains Frequency The average frequency measured on three
phases.
Motor kW
The motor's running power in kilowatts.
Motor HP
The motor's running power in horsepower.
Motor Temp
The motor's temperature, calculated by the
thermal model.
kWh
The number of kilowatt hours the motor has
run via the soft starter.
Hours Run
*
The number of hours the motor has run via
the soft starter.
8-5 User Screen - Bottom Right
Option:
Function:
Selects the item displayed in the bottom
right part of the screen.
Blank
*
Displays no data in the selected area,
allowing long messages to be shown without
overlapping.
Starter State
The starter's operating state (starting,
running, stopping or tripped). Only available
for “Top L” and “Btm L”.
Motor Current
The average current measured on three
phases.
Motor pf
The motor's power factor, measured by the
soft starter.
Mains Frequency The average frequency measured on three
phases.
Motor kW
The motor's running power in kilowatts.
Motor HP
The motor's running power in horsepower.
Motor Temp
The motor's temperature, calculated by the
thermal model.
kWh
The number of kilowatt hours the motor has
run via the soft starter.
Hours Run
The number of hours the motor has run via
the soft starter.
7.11.2 Performance Graphs
The loggings menu allows the user to view performance
information in real-time graphs.
The newest information is displayed at the right hand
edge of the screen. The graph can be paused to analyse
data by pressing and holding the OK button. To re-start
the graph, press and hold OK.
8-6 Graph Timebase
Option:
Function:
Sets the graph time scale. The graph will progres-
sively replace the old data with new data.
10 secs
*
30 secs
1 min
5 minutes
10 minutes
30 minutes
1 hour
8-7 Graph Maximum Adjustment
Range:
Function:
400%
*
[0% - 600%] Adjusts the upper limit of the performance
graph
8-8 Graph Minimum Adjustment
Range:
Function:
0%
*
[0% - 600%] Adjusts the lower limit of the performance
graph.
8-9 Mains Reference Voltage
Range:
Function:
400 V
*
[100 - 690
V]
Sets the nominal voltage for the LCP's
monitoring functions. This is used to
calculate motor kilowatts and kilovolt
amperes (kVA), but does not affect the MCD
500's motor control protection.
Enter the measured mains voltage.
Programming
MCD 500 Operating Instruction
64
MG17K402 - VLT
®
is a registered Danfoss trademark