5-2 Auto-Start Time
Range:
Function:
1 min
*
[00:01 - 24:00
(hrs:min)]
Sets the time for the soft starter to
auto-start, in 24 hour clock format.
5-3 Auto-Stop Type
Option: Function:
Selects whether the soft starter will auto-stop after a
specified delay, or at a time of day.
Off
*
The soft starter will not auto-stop.
Time The soft starter will auto-stop after a delay from the
next start, as specified in
5-4 Auto-stop Time
.
Clock The soft starter will auto-stop at the time programmed
in
5-4 Auto-stop Time
.
5-4 Auto-Stop Time
Range:
Function:
1 min
*
[00:01 -
24:00
(hrs:min)]
Sets the time for the soft starter to auto-
stop, in 24 hour clock format.
CAUTION
This function should not be used in
conjunction with remote two-wire
control. The soft starter will still
accept start and stop commands from
the remote inputs or serial communi-
cation network. To disable local or
remote control, use
3-1 Local/Remote
.
If auto-start is enabled and the user is
in the menu system, auto-start will
become active if the menu times out
(if no LCP activity is detected for five
minutes).
7.9 Auto-Reset
The MCD 500 can be programmed to automatically reset
certain trips, which can help minimise operating
downtime. Trips are divided into three categories for auto-
reset, depending on the risk to the soft starter:
Group
A
Current Imbalance
Phase Loss
Power Loss
Mains Frequency
B
Undercurrent
Instantaneous Overcurrent
Input A Trip
C
Motor Overload
Motor Thermistor
Starter Overtemperature
Table 7.7
Other trips cannot be automatically reset.
This function is ideal for remote installations using 2-wire
control in Auto On mode. If the 2-wire start signal is
present after an auto-reset, the MCD 500 will restart.
6-1 Auto-Reset Action
Option:
Function:
Selects which trips can be auto-reset.
Do not Auto-Reset
*
Reset Group A
Reset Group A & B
Reset Group A, B & C
6-2 Maximum Resets
Range:
Function:
1
*
[1 - 5] Sets how many times the soft starter will auto-reset,
if it continues to trip. The reset counter increases by
one each time the soft starter auto-resets, and
decreases by one after each successful start/stop
cycle.
NOTE
The reset counter will return to 0 if the starter is manually
reset.
7.9.1 Auto-Reset Delay
The MCD 500 can be configured to wait before auto-
resetting a trip. Separate delays can be set for trips in
Groups A and B, or in Group C.
6-3 Reset Delay Groups A & B
Range:
Function:
5 secs
*
[00:05 - 15:00
(min:secs)]
Sets the auto-reset delay for
Group A and Group B trips.
6-4 Reset Delay Group C
Range:
Function:
5 min
*
[5 - 60 (minutes)] Sets the auto-reset delay for Group C
trips.
7.10 Secondary Motor Set
7-1 Motor FLC-2
Range:
Function:
[Motor
dependent]
Matches the starter to the second motor's
full load current. Set to the full load
current (FLC) rating shown on the motor
nameplate.
Programming