![VIPA TP 107-CL Manual Download Page 14](http://html1.mh-extra.com/html/vipa/tp-107-cl/tp-107-cl_manual_1029248014.webp)
EMC
Standard
Comment
Emitted interference
EN 61000-6-4
Class A (Industrial area)
Noise immunity
zone B
EN 61000-6-2
Industrial area
EN 61000-4-2
ESD
8kV at air discharge (degree of severity 3),
4kV at contact discharge (degree of severity 2)
EN 61000-4-3
HF field immunity (casing)
80MHz … 1000MHz, 10V/m, 80% AM (1kHz)
1.4GHz ... 2.0GHz, 3V/m, 80% AM (1kHz)
2GHz ... 2.7GHz, 1V/m, 80% AM (1kHz)
EN 61000-4-6
HF conducted
150kHz … 80MHz, 10V, 80% AM (1kHz)
EN 61000-4-4
Burst, degree of severity 3
EN 61000-4-5
Surge, degree of severity 3 *
*) Due to the high-energetic single pulses with Surge an appropriate external protective circuit with lightning protection elements like conductors for lightning and overvoltage is
necessary.
2.6 Technical data
Order no.
H71-L1A41-0
Type
cloudPanel TP107-CL
Display
Display size (diagonal)
7 "
Display size (width)
155 mm
Display size (height)
88 mm
Resolution
480 x 800 / 800 x 480
Aspect ratio
16:9
Type of display
TFT color (64K colors)
MTBF Backlights (25°C)
20000 h
System properties
Processor
Cortex-A8 1000 MHz
Operating system
Linux 3.12
User software
Webkit Browser
Work memory
512 MB
User memory
4 GB
Available memory (user data)
700 MB
SD/MMC Slot
-
CF Card Slot Typ II
-
VIPA HMI
Hardware description
Technical data
HB160 | TP-cloud | H71-L1A41-0 | en | 18-02
14