Chapter 6 DeviceNet
Manual VIPA System 200V
6-16
HB97E - IM - Rev. 06/29
I/O addressing of the DeviceNet scanner
The DeviceNet coupler determines the modules installed on the backplane
bus automatically and uses the result to generate the number of input and
output bytes.
You have to determine these two values when you configure the
input/output modules and enter them in the DeviceNet scanner (master):
•
produced connection size (number of input bytes)
•
consumed connection size (number of output bytes)
The addressing results from the sequence of the modules (plug-in location
1 to 32) and the base address that was defined in the DeviceNet scanner
for the bus coupler.
•
Set the DeviceNet scanner to connection type POLL IO.
•
Define the parameters:
"Receive data size" = number of input bytes
"Transmit data size" = number of output bytes
•
Define the base address (mapping) of receive data and transmit data as
required.
•
Activate the DeviceNet coupler IM 253DN in the scan list.
•
Start the DeviceNet scanner.
When the DeviceNet scanners have been configured, the input and output
modules are accessible via the defined addresses.
The following 6 modules have been installed into the backplane bus:
Plug-in
location
Installed module
Input data
Output data
Slot 0
DeviceNet coupler
-
-
Slot 1
Digital Out SM 222
1Byte
Slot 2
Digital Out SM 222
1Byte
Slot 3
Digital In SM 221
1Byte
Slot 4
Analog In SM 231
4Words
Slot 5
Analog Out SM 232
4Words
Total:
1+4*2=9Byte
1+1+4*2=10Byte
The result is:
•
produced connection size: 9Byte (sum of input bytes)
•
consumed connection size: 10Byte (sum of output bytes)
DeviceNet scanner
configuration
Example
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...