Manual VIPA System 200V
Chapter 2 Assembly and installation guidelines
HB97E - IM - Rev. 06/29
2-5
Assembly
Please follow these rules during the assembly!
•
Turn off the power supply before you insert or remove any modules!
•
Make sure that a clearance of at least 60mm exists above and 80mm
below the middle of the bus rail.
80 m
m
60 m
m
•
Every row must be completed from left to right and it has to start with a
header module (PC, CPU, and bus coupler).
1
2
4
3
•
Modules are to install adjacent to each other. Gaps are not permitted
between the modules since this would interrupt the backplane bus.
•
A module is only installed properly and connected electrically when it
has clicked into place with an audible click.
•
Plug-in locations after the last module may remain unoccupied.
Note!
A maximum of 32 modules can be connected at the back plane bus. Take
attention that here the maximum
sum current
of
3.5A
is not exceeded.
[1] Header
module,
like PC, CPU, bus
coupler, if double
width
[2] Header
module
(single width)
[3] Peripheral
module
[4] Guide
rails
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...