![VIPA SLIO System FM 050-1BA10 Manual Download Page 19](http://html1.mh-extra.com/html/vipa/slio-system-fm-050-1ba10/slio-system-fm-050-1ba10_manual_1029237019.webp)
Manual VIPA System SLIO
Chapter 1 Basics and Assembly
HB300E - FM - RE_050-1BA10 - Rev. 10/30
1-11
Wiring
DC24V
0V
DC24V
0V
1
2
DC24V max. 10A
SysDC5V max. 3A
[1] DC 24V Power section supply I/O area
[2] DC 24V for Electronic power supply bus coupler and I/O area
Note!
Power section and electronic power section supply are internally protected
against higher voltage by fuses. The fuses are within the power module.
If one fuse released, its electronic module must be exchanged!
It is recommended to externally protect the power section supply with a fast
10A fuse and the electronic power supply with a fast 4A fuse.
After PowerON of the System SLIO the LEDs RUN respectively MF get on
so far as the sum current does not exceed 3A.
With a sum current greater than 3A the LEDs may not be activated.
Here the power module with the order number 007-1AB10 is to be placed
between the peripheral modules. More concerning this may be found at the
following page.
Standard wiring
State of the
electronic power
supply via LEDs