Manual VIPA System SLIO
Chapter 3 Deployment
HB300E - FM - RE_050-1BB00 - Rev. 10/30
3-5
In-/Output area
The following areas of the in-/output area are used by the 050-1BB00:
At CPU, Profibus and ProfiNET the input respectively output area is
embedded to the corresponding address area.
IX = Index for access via CANopen with s = subindex, depends on number
and type of counter
SX = Subindex for access via EtherCAT
Addr.
Name
Bytes Function
IX
SX
+0
CV_I
4
Counter 0: Counter value 5400h/s
01h
+4
CV_II
4
Counter 1: Counter value 5401h/s+1 02h
+8
CSTS_I
2
Counter 0: Counter status 5402h/s
03h
+10
CSTS_II
2
Counter 1: Counter status 5403h/s+1 04h
The
counter value
always contains the current value of the corresponding
counter.
Bit
Name
Function
0 -
reserved
1
STS_CTRL_COMP is set when
comparison bit
is enabled
2
STS_SW-GATE Status software gate
(set when
SW gate
is active)
3 ... 4
-
reserved
5
STS_GATE
Status internal gate
(set when internal gate is active)
6 STS_COMP
Status
comparison bit
7
STS_C_DN
Status set at counter direction backward
8
STS_C_UP
Status set at counter direction forward
9
STS_CMP*
Status comparison is set when the comparison
condition is met. If comparison is
parameterized
never
, the bit is never set.
10
STS_END*
Status is set when
end value
was reached
11
STS_OFLW*
Status is set at overflow
12
STS_UFLW*
Status is set at underflow
13
STS_ZP*
Status is set at zero run
14 ... 15
-
reserved
*
The bits remain set until reset with RES_SET (bit 6
control word
).
Overview
Input area
12byte
CV_I
CV_II
Counter value
CSTS_I
CSTS_II
Counter status
Summary of Contents for SLIO FM 050-1BB00
Page 1: ...VIPA System SLIO FM 050 1BB00 Manual HB300E_FM RE_050 1BB00 Rev 10 30 July 2010...
Page 4: ...Contents Manual VIPA System SLIO ii HB300E FM RE_050 1BB00 Rev 10 30...
Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E FM RE_050 1BB00 Rev 10 30...
Page 56: ...Chapter 3 Deployment Manual VIPA System SLIO 3 24 HB300E FM RE_050 1BB00 Rev 10 30...