VIPA SLIO FM 050-1BB00 Manual Download Page 26

Chapter 1   Basics and Assembly

 

Manual VIPA System SLIO 

1-18 

 

HB300E - FM - RE_050-1BB00 - Rev. 10/30 

General data 

 

Conformity and approval 

Conformity 
CE 73/23/EWG 

Low-voltage 

directive 

Approval 
UL 

UL 508 

Approval for USA and Canada 

others 
RoHs 

Product is unleaded 

 

Protection of persons and device protection 

Type of protection 

IP20 

Electrical isolation 
to the field bus 

electrically isolated 

to the process level 

electrically isolated 

Insulation resistance 

EN 61131-2 

Insulation voltage to reference earth 
Inputs / outputs 

AC / DC 50V,  
test voltage AC 500V 

Protective measures 

against short circuit 

 

Environmental conditions to EN 61131-2 

Climatic 
Storage / transport 

EN 60068-2-14 

-25…+70°C 

Operation 
Horizontal installation 

EN 61131-2 

0…+60°C 

Vertical installation 

EN 61131-2 

0…+60°C 

Air humidity 

EN 60068-2-30 

RH1  
(without condensation, rel. humidity 10 … 95%) 

Pollution 

EN 61131-2 

Degree of pollution 2 

Mechanical 

Oscillation EN 

60068-2-6 

1G 

Shock EN 

60068-2-27 

15G 

 

Mounting conditions 

Mounting place 

In the control cabinet 

Mounting position 

Horizontal and vertical 

 

EMC 

Standard 

Comment 

Emitted 
interference 

EN 61000-6-4 

Class A (Industry area) 

 
 

Industry area 

EN 61000-4-2 

ESD 
Degree of severity 3, i.e. 8kV at air discharge,  
4kV at contact discharge  

EN 61000-4-3 

HF irradiation (casing) 
80MHz … 1000MHz, 10V/m 80% AM (1kHz) 

EN 61000-4-6 

HF conducted  
150kHz … 80MHz, 10V/m 
80% AM (1kHz) 

EN 61000-4-4 

Burst, degree of severity 3 

Noise immunity 
zone B 

EN 61000-6-2  

EN 61000-4-5 

Surge, degree of severity 3 

 

 

Summary of Contents for SLIO FM 050-1BB00

Page 1: ...VIPA System SLIO FM 050 1BB00 Manual HB300E_FM RE_050 1BB00 Rev 10 30 July 2010...

Page 2: ...c Compatibility Directive 2006 95 EC Low Voltage Directive Conformity is indicated by the CE marking affixed to the product Conformity Information For more information regarding CE marking and Declara...

Page 3: ...m conception 1 3 Dimensions 1 6 Installation 1 7 Wiring 1 11 Trouble shooting LEDs 1 14 Installation guidelines 1 15 General data 1 18 Chapter 2 Hardware description 2 1 Properties 2 2 Structure 2 3 T...

Page 4: ...Contents Manual VIPA System SLIO ii HB300E FM RE_050 1BB00 Rev 10 30...

Page 5: ...of the VIPA System SLIO Here you will find the information required to assemble and wire a controller system consisting of System SLIO components Besides the dimensions the general technical data of...

Page 6: ...lowing guides are available in the manual an overall table of contents at the beginning of the manual an overview of the topics for every chapter The manual is available in printed form on paper in el...

Page 7: ...anual must be available to all personnel in the project design department installation department commissioning operation The following conditions must be met before using or commissioning the compone...

Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E FM RE_050 1BB00 Rev 10 30...

Page 9: ...e information required to assemble and wire a controller system consisting of System SLIO components Besides the dimensions the general technical data of System SLIO will be found Topic Page Chapter 1...

Page 10: ...ge components thereby causing the module to become inoperable or unusable Modules that have been damaged by electrostatic discharges can fail after a temperature change mechanical shock or changes in...

Page 11: ...y the electronic power supply may be extended with 2A The System SLIO consists of the following components Bus coupler Periphery modules Power modules Accessories With a bus coupler bus interface and...

Page 12: ...nic module which is mounted to the terminal module by a save sliding mechanism With an error the defective module may be exchanged for a functional module with standing installation By an integrated c...

Page 13: ...nderneath the terminal of the terminal module With a flat mounting rail for adaption to a flat mounting rail you may remove the spacer of the shield bus carrier With each bus coupler to protect the ba...

Page 14: ...bly Manual VIPA System SLIO 1 6 HB300E FM RE_050 1BB00 Rev 10 30 Dimensions 104 109 76 5 48 5 104 109 76 5 15 133 12 9 58 62 12 9 Dimensions in mm Dimensions bus coupler Dimensions periphery module Di...

Page 15: ...odule The module is fixed to the mounting rail by pushing downwards the locking lever The modules may either separately be mounted to the mounting rail or as block Here is to be considered that each l...

Page 16: ...with 2A More about this may be found at Wiring Mount the mounting rail Please consider that a clearance from the middle of the mounting rail of at least 80mm above and 60mm below respectively 80mm by...

Page 17: ...ver may now be mounted at the last module The shield bus carrier available as accessory serves to carry the shield bus to connect cable shields The shield bus carrier is mounted underneath the termina...

Page 18: ...ripes at both sides to the mounting rail 1 2 3 4 With mounting respectively de mounting of a module group you also have to remove the electronic module of the just mounted right module After mounting...

Page 19: ...e If one fuse released its electronic module must be exchanged It is recommended to externally protect the power section supply with a fast 10A fuse and the electronic power supply with a fast 4A fuse...

Page 20: ...at the following backplane bus modules may be placed with a sum current of max 2A Afterwards the power module 007 1AB10 is to be placed again 007 1AB00 Sys DC 5V DC 24V 10A 007 1AB00 Sys DC 5V DC 24V...

Page 21: ...shields The shield bus carrier is mounted underneath the terminal of the terminal module With a flat mounting rail for adaption to a flat mounting rail you may remove the spacer of the shield bus carr...

Page 22: ...er module 007 1AB10 More concerning this may be found above at Wiring RUN MF RUN MF RUN MF RUN MF RUN MF RUN MF RUN MF RUN MF RUN MF RUN MF Behavior After PowerON the MF LED of one module respectively...

Page 23: ...rferencing the environment All System SLIO components are developed for the deployment in hard industrial environments and fulfill high demands on the EMC Nevertheless you should project an EMC planni...

Page 24: ...g lines must be laid isolated When transmitting signals with small amplitudes the one sided laying of the isolation may be favorable Lay the line isolation extensively on an isolation protected earth...

Page 25: ...ation one sided Then you only achieve the absorption of the lower frequencies A one sided isolation connection may be convenient if the conduction of a potential compensating line is not possible anal...

Page 26: ...tic Storage transport EN 60068 2 14 25 70 C Operation Horizontal installation EN 61131 2 0 60 C Vertical installation EN 61131 2 0 60 C Air humidity EN 60068 2 30 RH1 without condensation rel humidity...

Page 27: ...on In this chapter the counter module 050 1BB00 of the System SLIO is described Here every information about the hardware components of the module may be found The technical data are at the end of the...

Page 28: ...ounting frequency max 400kHz AB 1 2 4 fold evaluation or pulse and direction Comparison value set value input filter configurable Interrupt and diagnostics function with s time stamp s time stamp for...

Page 29: ...ption RUN green RUN MF MF red Bus communication is OK Module status is OK Bus communication is OK Module status reports an error Bus communication is not possible Module status reports an error Error...

Page 30: ...ctively track A of an encoder for 1 2 or 4 fold evaluation 2 DC 24V O DC 24V for encoder 3 0V O GND 4 A1 I Counter 1 A pulse Pulse input for counter signal respectively track A of an encoder for 1 2 o...

Page 31: ...imultaneously utilizable vertical 4 Input characteristic IEC 61131 type 1 Input data size 12Byte Technical data digital outputs Number of outputs Cable length shielded Cable length unshielded Rated lo...

Page 32: ...rameterizable Diagnostic functions yes parameterizable Diagnostics information read out possible Module state green LED Module error display red LED Channel error display none Isolation Between channe...

Page 33: ...oyment of the System SLIO counter module 050 1BB00 is described Here every information required for the deployment may be found Topic Page Chapter 3 Deployment 3 1 Fast introduction 3 2 In Output area...

Page 34: ...Counter 0 Comp value 5600h s 01h 4 CC_II 4 Counter 1 Comp value 5600h s 1 02h 8 CCTRL_I 2 Counter 0 Control word 5602h s 03h 10 CCTRL_II 2 Counter 1 Control word 5602h s 1 04h Bit Name Function 0 rese...

Page 35: ...Input frequency track A 02h 01h 3103h 04h CH3B 1 C1 Input frequency track B 02h 01h 3104h 05h INT_I 1 C0 Interrupt behavior 00h 80h 3105h 06h FCT_I 1 C0 Counter function 00h 80h 3106h 07h MODE2_I 1 C0...

Page 36: ...ge 0 1 SW_GATE_RESET in the control word The following behavior for the comparison bit STS_COMP in the counter status may be set via the parameterization No comparison Comparison bit is not influenced...

Page 37: ...current value of the corresponding counter Bit Name Function 0 reserved 1 STS_CTRL_COMP is set when comparison bit is enabled 2 STS_SW GATE Status software gate set when SW gate is active 3 4 reserve...

Page 38: ...er value The behavior of the comparison bit STS_COMP in the counter status res the process interrupt has to be set for counter 0 via the parameter INT_I and INT_II for counter 1 Bit Name Function 0 re...

Page 39: ...7h MODE2_I 1 C0 Counter mode 2 00h 80h 3107h 08h MODE3_I 1 C0 Counter mode 3 00h 80h 3108h 09h SET_I 4 C0 Set value 00h 81h 3109h 310Ch 0Ah END_I 4 C0 End value 00h 81h 310Dh 3110h 0Bh LOAD_I 4 C0 Loa...

Page 40: ...flow Bit 4 Proc interrupt comparison value Bit 5 Proc interrupt end value Bit 7 6 0 fix Setting the appropriate bit activates the associated process interrupt Byte Bit 7 0 0 Bit 5 0 Counter function 0...

Page 41: ...counting is continued with the count There is the possibility to preset each counter with a set value The value is kept by the counter by a changing edge 0 1 of the bit COUNTERVAL_SET in the control...

Page 42: ...counting range is available Limits Valid value range Lower count limit 2 147 483 648 231 Upper count limit 2 147 483 647 231 1 Main counting direction forward Upper restriction of the count range The...

Page 43: ...another counting pulse in negative direction arrives it jumps to the upper count limit and counts from there on The count limits are set to the maximum count range Limits Valid value range Lower count...

Page 44: ...triggered To restart the count process you have to re open the internal gate At interrupting gate control the count process continuous with the last recent counter value At aborting gate control the...

Page 45: ...alue lower counter limit load value 0 overflow underflow time counter value gate stop automatically gate stop automatically gate start gate start Main counting direction backwards The counter counts b...

Page 46: ...231 1 upper counter limit load value 0 gate start time counter value gate stop lower counter limit overflow underflow zero crossing Main counting direction forward The counter counts forward starting...

Page 47: ...hes the end value 1 in negative direction it jumps to the load value at the next negative count pulse If enabled additionally a process interrupt is triggered You may exceed the upper count limit Limi...

Page 48: ...digital output res releases a process interrupt depending on the counter value Hysteresis The setting of a hysteresis avoids for example a high interrupt toggling when the value of an encoder signal...

Page 49: ...I gate was automatically closed at counting once so this may only be opened with an edge 0 1 on SW_GATE_SET The following states influence the I gate SW gate influences I gate 0 0 1 1 with edge 0 1 1...

Page 50: ...omparison bit is set when counter value comparison value The comparison bit remains set as long as the counter value is higher or equal comparison value Comparison bit is set when counter value compar...

Page 51: ...Comparison bit Hysteresis 0 Hysteresis 3 Counter value 1 2 3 4 5 6 7 1 Counter value comparison value comparison bit is set and hysteresis activated 2 Leave hysteresis range comparison bit is reset 3...

Page 52: ...nd hysteresis activated 4 Comparison bit is reset for leaving hysteresis range and counter value comparison value 5 Counter value comparison value comparison bit is set and hysteresis activated 6 Coun...

Page 53: ...nterrupt data were transferred via diagnostics telegram SX Subindex for access via EtherCAT Name Bytes Function Default SX PRIT_A 1 Process interrupt 00h 02h PRIT_B 1 State of the inputs 00h 03h PRIT_...

Page 54: ...X Index for access via CANopen The access happens by IX 2F01h Additionally the first 4 bytes may be accessed by IX 2F00h SX Subindex for access via EtherCAT Name Bytes Function Default DS IX SX ERR_A...

Page 55: ...module here 02h Byte Bit 7 0 0 Bit 0 set at error in channel group 0 Bit 1 set at error in channel group 1 Bit 7 2 reserved Byte Bit 7 0 0 Diagnostic interrupt due to process interrupt lost at Bit 0...

Page 56: ...Chapter 3 Deployment Manual VIPA System SLIO 3 24 HB300E FM RE_050 1BB00 Rev 10 30...

Reviews: