background image

Technical Documents 

 

VIPA GmbH 

·

 Ohmstr. 4 

· 

D-91074-Herzogenaurach 

· 

Ph.:+49-9132-744-0 

· 

Fax:+49-9132-744-1864 

· 

www.vipa.de 

 

 

 

 

Technical  

Documents 

 

Interbus 

Diagnostics Device 

342-0IA00 

 
 

Order-No.: VIPA HB144E_IBS-DIAG 

Reference: RE_342-0IA00 

Rev. 09/22 

 

 

General Information 

The diagnostics device VIPA 342-0IA00 serves for connection to an Interbus (IBS) master module from VIPA with Mini-
DIN diagnostics jack. By means of the diagnostics device operation and fault conditions may be represented, recognized 
and localized. For this the device has a multi-line LCD display for display and a key field for menu-assisted service. The 
hardware platform of the diagnostics device (USC/4-DIAG-L) comes from Phoenix Contact as like the IBS hardware 
platform of the master (USC4-2). In the following the single components are described only briefly. In the "Diagnostics 
guide" of Phoenix Contact a detailed description of the diagnostics possibilities may be found. 

 

Connect the diagnostics device 

The diagnostics device is directly supplied by the Mini-DIN jack of the IBS master and is ready for
operation after connection. Please consider that the arrow on the plug  

  shows to the right side

when the diagnostics device is connected to the Mini-DIN jack. 

 

 

 

 

Attention! 

Please consider the sufficient grounding when connecting the diagnostics device.
Hardware-caused there is the risk to come in contact to a pin of the plug while the
diagnostics device is connected. This could damage the device by an electrostatic
discharge. 

 

LCD-Display 

The diagnostics display consists of the following components: 

• 

3 main lines to display operating states, addresses and data. 

• 

16 status segments on the left side of the display for binary representation of input and output data. 

• 

CPU STOP status indicator (Arrow is displayed). 

• 

Red (error) or green (normal operation) background illumination, depending on the operating state of the bus. 

 

[1] FAIL 

Indicates that an error has occurred and provides information 
about the error type. 

 

 

CTRL Controller 

error 

 

 

RBUS 

Remote bus error 

 

 

LBUS 

Local bus error 

 

 

BUS 

General bus error 

 

 

OUT1 

Error at the outgoing interface 

 

 

OUT2 

Error at the branching interface 

 

 

DEV Device 

error 

 

 

PF Peripheral 

fault 

 MODE 

When MODE active, further menu items may be selected. 

 MONI 

Indicates that monitor mode is activated. 

1

2

3

4

5

0
.
.
.
.
.
.
7

0
.
.
.
.
.
.
7

STOP

6

 

 HEX 

The value in the 1. main line is displayed in hexadecimal notation. 
If the HEX segment is not activated, the value is displayed in 
decimal notation. 

 