Technical Documents
VIPA GmbH
·
Ohmstr. 4
·
D-91074-Herzogenaurach
·
Ph.:+49-9132-744-0
·
Fax:+49-9132-744-1864
·
www.vipa.de
Technical
Documents
Interbus
Diagnostics Device
342-0IA00
Order-No.: VIPA HB144E_IBS-DIAG
Reference: RE_342-0IA00
Rev. 09/22
General Information
The diagnostics device VIPA 342-0IA00 serves for connection to an Interbus (IBS) master module from VIPA with Mini-
DIN diagnostics jack. By means of the diagnostics device operation and fault conditions may be represented, recognized
and localized. For this the device has a multi-line LCD display for display and a key field for menu-assisted service. The
hardware platform of the diagnostics device (USC/4-DIAG-L) comes from Phoenix Contact as like the IBS hardware
platform of the master (USC4-2). In the following the single components are described only briefly. In the "Diagnostics
guide" of Phoenix Contact a detailed description of the diagnostics possibilities may be found.
Connect the diagnostics device
The diagnostics device is directly supplied by the Mini-DIN jack of the IBS master and is ready for
operation after connection. Please consider that the arrow on the plug
shows to the right side
when the diagnostics device is connected to the Mini-DIN jack.
Attention!
Please consider the sufficient grounding when connecting the diagnostics device.
Hardware-caused there is the risk to come in contact to a pin of the plug while the
diagnostics device is connected. This could damage the device by an electrostatic
discharge.
LCD-Display
The diagnostics display consists of the following components:
•
3 main lines to display operating states, addresses and data.
•
16 status segments on the left side of the display for binary representation of input and output data.
•
CPU STOP status indicator (Arrow is displayed).
•
Red (error) or green (normal operation) background illumination, depending on the operating state of the bus.
[1] FAIL
Indicates that an error has occurred and provides information
about the error type.
CTRL Controller
error
RBUS
Remote bus error
LBUS
Local bus error
BUS
General bus error
OUT1
Error at the outgoing interface
OUT2
Error at the branching interface
DEV Device
error
PF Peripheral
fault
MODE
When MODE active, further menu items may be selected.
MONI
Indicates that monitor mode is activated.
1
2
3
4
5
0
.
.
.
.
.
.
7
0
.
.
.
.
.
.
7
STOP
6
HEX
The value in the 1. main line is displayed in hexadecimal notation.
If the HEX segment is not activated, the value is displayed in
decimal notation.