Chapter 3   Deployment 

HB300E - IM - RE_053-1DP00 - Rev. 11/03 

 

3-29 

The interrupt section of the slave diagnostic shows information about 
interrupt type and cause. It consists of max. 20byte. For every slave 
diagnostic max. 1 interrupt can be send. The interrupt section is always the 
last part of the diagnostic telegram if activated it in the parameterization. 
 
Depending on the interrupt type, the interrupt section has the following 
structure: 

Byte 

Element 

Description 

x...x+3 

Interrupt status  Contains information about the interrupt type

x+4...x+19 Diagnostic 

interrupt 

The 16byte correspond to the record set 1 of 
the CPU diagnostic 

x+4...x+7 Hardware 

interrupt 

The 4byte are module specific and are 
described with the according module. 

 

If there is a diagnostic event for channel/group 0 of a module, there may be 
a module error as well as a channel error. The entry is made in this case 
even if you have not enabled the diagnostic for channel (/channel group) 0 
of a module. 
The interrupt section is structured as follows: 
 

Interrupt status byte x ... x+3 

Byte 

Bit 7 ... Bit 0 

Bit 5 ... 0:  010100: Length of the interrupt section incl. byte x 
Bit 7 ... 6:  00 (fix) Code for Module-related diagnostic 

x+1 

Bit 6 ... 0:  Type of interrupt 

 

    0000001: 

Diagnostic 

interrupt 

     

0000010: Hardware interrupt  

Bit 7: Code for interrupt 

x+2 

Bit 7 ... 0:  Slot of the module that is producing interrupt 1 ... 64 

x+3 

Bit 1, 0: 

00: Hardware interrupt 

    01: 

Diagnostic 

interrupt

 incoming 

    10: 

Diagnostic 

interrupt

 outgoing

 

    11: 

reserved 

Bit 2: 0 (fix) 
Bit 7 ... 3:  interrupt sequence number 0 …31 

 

 

Interrupts 

Structure 

Interrupt status 

Summary of Contents for 053-1DP00

Page 1: ...VIPA System SLIO IM 053 1DP00 Manual HB300E_IM RE_053 1DP00 Rev 11 03 January 2011...

Page 2: ...c Compatibility Directive 2006 95 EC Low Voltage Directive Conformity is indicated by the CE marking affixed to the product Conformity Information For more information regarding CE marking and Declara...

Page 3: ...1 3 Dimensions 1 6 Installation 1 7 Wiring 1 11 Trouble shooting LEDs 1 14 Installation guidelines 1 15 General data 1 18 Chapter 2 Hardware description 2 1 Properties 2 2 Structure 2 3 Technical dat...

Page 4: ...Contents Manual VIPA System SLIO ii HB300E IM RE_053 1DP00 Rev 11 03...

Page 5: ...le and wire a controller system consisting of System SLIO components Besides the dimensions the general technical data of System SLIO will be found Chapter 2 Hardware description Here the hardware com...

Page 6: ...rs Every chapter provides a self contained description of a specific topic The following guides are available in the manual an overall table of contents at the beginning of the manual an overview of t...

Page 7: ...anual must be available to all personnel in the project design department installation department commissioning operation The following conditions must be met before using or commissioning the compone...

Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E IM RE_053 1DP00 Rev 11 03...

Page 9: ...e information required to assemble and wire a controller system consisting of System SLIO components Besides the dimensions the general technical data of System SLIO will be found Topic Page Chapter 1...

Page 10: ...ge components thereby causing the module to become inoperable or unusable Modules that have been damaged by electrostatic discharges can fail after a temperature change mechanical shock or changes in...

Page 11: ...tronic power supply may be extended with 2A The System SLIO consists of the following components Bus coupler Periphery modules Power modules Accessories With a bus coupler bus interface and power modu...

Page 12: ...nic module which is mounted to the terminal module by a save sliding mechanism With an error the defective module may be exchanged for a functional module with standing installation By an integrated c...

Page 13: ...ted underneath the terminal of the terminal module With a flat mounting rail for adaption to a flat mounting rail you may remove the spacer of the shield bus carrier With each bus coupler to protect t...

Page 14: ...Manual VIPA System SLIO 1 6 HB300E IM RE_053 1DP00 Rev 11 03 Dimensions 104 109 76 5 48 5 49 104 109 76 5 15 133 12 9 55 5 62 12 9 Dimensions in mm Dimensions bus coupler Dimensions periphery module...

Page 15: ...odule The module is fixed to the mounting rail by pushing downwards the locking lever The modules may either separately be mounted to the mounting rail or as block Here is to be considered that each l...

Page 16: ...with 2A More about this may be found at Wiring Mount the mounting rail Please consider that a clearance from the middle of the mounting rail of at least 80mm above and 60mm below respectively 80mm by...

Page 17: ...module you have to mount the bus cover now The shield bus carrier available as accessory serves to carry the shield bus to connect cable shields The shield bus carrier is mounted underneath the termin...

Page 18: ...ripes at both sides to the mounting rail 1 2 3 4 With mounting respectively de mounting of a module group you also have to remove the electronic module of the just mounted right module After mounting...

Page 19: ...s to be externally protected with a fuse fast which corresponds to the maximum current This means max 10A is to be protected with a 10A fuse fast The electronic power supply for bus coupler and I O ar...

Page 20: ...a sum current of max 2A Afterwards the power module 007 1AB10 is to be placed again To secure the power supply the power modules may be mixed used 007 1AB00 Sys DC 5V DC 24V 10A 007 1AB00 Sys DC 5V D...

Page 21: ...s The shield bus carrier is mounted underneath the terminal of the terminal module With a flat mounting rail for adaption to a flat mounting rail you may remove the spacer of the shield bus carrier Af...

Page 22: ...place the power module 007 1AB10 More concerning this may be found above at Wiring RUN MF RUN MF RUN MF RUN MF RUN MF RUN MF RUN MF RUN MF RUN MF RUN MF Behavior After PowerON the MF LED of one module...

Page 23: ...nterferencing the environment All System SLIO components are developed for the deployment in industrial environments and fulfill high demands on the EMC Nevertheless you should project an EMC planning...

Page 24: ...g lines must be laid isolated When transmitting signals with small amplitudes the one sided laying of the isolation may be favorable Lay the line isolation extensively on an isolation protected earth...

Page 25: ...ation one sided Then you only achieve the absorption of the lower frequencies A one sided isolation connection may be convenient if the conduction of a potential compensating line is not possible anal...

Page 26: ...C Vertical installation EN 61131 2 0 60 C Air humidity EN 60068 2 30 RH1 without condensation rel humidity 10 95 Pollution EN 61131 2 Degree of pollution 2 Mechanical Oscillation EN 60068 2 6 1G Shock...

Page 27: ...11 03 2 1 Chapter 2 Hardware description Here the hardware components of the IM 053 1DP00 are more described You will find the technical data at the end of this chapter Topic Page Chapter 2 Hardware...

Page 28: ...BUS transfer rates Integrated DC 24V power supply for power and electronic section supply of the periphery modules 1 MSAC_C1 connection Read Write with 244byte data 4byte DP V1 header 240byte user dat...

Page 29: ...wer module Bus interface Terminal Address selector LED Color Description PWR green Bus interface is power supplied SF red Station fault structure is not corresponding to the configuration DE green Sta...

Page 30: ...ly 3 0V I GND for power section supply 4 Sys DC 24V I DC 24V for electronic section supply 5 not connected 6 DC 24V I DC 24V for power section supply 7 0V I GND for power section supply 8 Sys 0V I GND...

Page 31: ...xD N A Slave RxD TxD P B RxD TxD N A 5 3 8 6 Shield Shield Note Please consider to terminate the last participants on the bus at both ends by activating the terminating resistor Valid address may rang...

Page 32: ...nostics information read out possible Supply voltage display green LED Group error display red LED Channel error display none Hardware configuration Racks max 1 Modules per rack max 64 Number of digit...

Page 33: ...ay find here every information about assembly and project engineering The chapter closes with the description of the PROFIBUS installation guidelines and the diagnostic functions Topic Page Chapter 3...

Page 34: ...S DP is a special protocol intended mainly for automation tasks in a manufacturing environment DP is very fast offers Plug n Play facilities and provides a cost effective alternative to parallel cabli...

Page 35: ...hery and the high level master In accordance with the PROFIBUS standards these devices have no bus access rights They are only allowed to acknowledge messages or return messages to a master when this...

Page 36: ...n a predefined and repetitive cycle by the master You assign a slave to a specific master when you define the project You can also define which DP slaves are included and which are excluded from the c...

Page 37: ...aves all the input data from the modules in the PII and all the output data from the PIQ in the output modules When the data has been saved the PII is transferred into the buffer send and the contents...

Page 38: ...e 2 Slave 3 The DPM 1 Master Class 1 has the token and is able to send messages to or retrieve them from slave 1 then slave 2 etc in a fixed sequence until it reaches the last slave of the current lis...

Page 39: ...ddresses data of the PROFIBUS coupler Slot_Number 0 addresses the data of the function modules 0 1 2 3 4 Slot_Number Data structure 1Byte Output Modul 1 1Byte Output Modul 2 1Byte Input Modul 3 4Byte...

Page 40: ...edge The master acknowledges receipt of an alarm to the slave Status A status message is transmitted from the slave to the master There is no acknowledgment Data transmission is connection oriented ov...

Page 41: ...y been commissioned Any failures of stations or new devices are detected automatically Every device on the PROFIBUS is identified by an address This address must be an unique number in the bus system...

Page 42: ...ne help of the according engineering tool Structure and content of the GSD file are dictated by the PROFIBUS User Organization PNO and may be retrieved there To set respectively change parameters duri...

Page 43: ...h max 240 8bit Data Response with length DP V1 Write Response 0x5F 8bit Slot_Number 8bit Index DS 8bit Length 8bit The parameters are activated as soon as they where transferred Note The parameter rec...

Page 44: ...odule description 3 Bit 5 0 reserved Bit 6 Hardware interrupt lost Bit 7 reserved 4 Channel type 70h Module with digital inputs 71h Module with analog inputs 72h Module with digital outputs 73h Module...

Page 45: ...mber GSD file VIPA 053 1DP00 DP V0 VI000C19 gsd VIPA 053 1DP00 DP V1 VI010C19 gsd Please install the required files into your configuration tool Details on the installation of the GSD and or type file...

Page 46: ...entifier related diagnostic enable 1 Identifier related diagnostic disable Bit 1 0 Module status enable 1 Module status disable Bit 2 0 Channel related diagnostic enable 1 Channel related diagnostic d...

Page 47: ...e Bit 7 0 fix 70h 2 08h fix 08h 3 0Ah fix 0Ah 4 81h fix 81h 5 00h fix 00h 6 00h fix 00h 7 Bit 0 0 Identifier related diagnostic enable 1 Identifier related diagnostic disable Bit 1 0 Module status ena...

Page 48: ...lishment To access the DP V1 slave with the Siemens SIMATIC manager the diagnostic address which can be set by properties is used as ID Using the following record set no as Index you get access for re...

Page 49: ...ead module process image 50h R Device name as ASCII code 51h R Hardware version as ASCII code 52h R Software version as ASCII code is only shown with analog modules 53h R Serial number of the device u...

Page 50: ...ored during project engineering By means of I M data the modules can online be identified Note Only one DP master may access at one time the I M data The data structure of the I M data corresponds to...

Page 51: ...N read 2byte 0101h Information about the version of the I M data 0101h version 1 1 IM_SUPPORTED read 2byte 001Fh Information about available I M Data IM_INDEX 650000 65004 Maintenance data 1 IM_INDEX...

Page 52: ...nable As transfer medium PROFIBUS uses an isolated twisted pair cable based upon the RS485 interface The RS485 interface is working with voltage differences Though it is less irritable from influences...

Page 53: ...s to be terminated with its ripple resistor Please make sure to terminate the last participants on the bus at both ends by activating the terminating resistor In systems with more than two stations al...

Page 54: ...switch that is used to activate a terminating resistor Attention The terminating resistor is only effective if the connector is installed at a slave and the slave is connected to a power supply Note A...

Page 55: ...gnostic data are prepended to the diagnostic bytes More detailed information to the structure of the slave standard diagnostic data is to find in the standard papers of the PROFIBUS User Organization...

Page 56: ...module on slot 3 Bit 3 Entry for module on slot 4 Bit 4 Entry for module on slot 5 Bit 5 Entry for module on slot 6 Bit 6 Entry for module on slot 7 Bit 7 Entry for module on slot 8 X 2 Bit 0 Entry fo...

Page 57: ...module on slot 44 Bit 4 Entry for module on slot 45 Bit 5 Entry for module on slot 46 Bit 6 Entry for module on slot 47 Bit 7 Entry for module on slot 48 X 7 Bit 0 Entry for module on slot 49 Bit 1 E...

Page 58: ...status module slot 8 X 6 Bit 1 0 Module status module slot 9 Bit 3 2 Module status module slot 10 Bit 5 4 Module status module slot 11 Bit 7 6 Module status module slot 12 X 7 Bit 1 0 Module status m...

Page 59: ...46 Bit 5 4 Module status module slot 47 Bit 7 6 Module status module slot 48 X 16 Bit 1 0 Module status module slot 49 Bit 3 2 Module status module slot 50 Bit 5 4 Module status module slot 51 Bit 7...

Page 60: ...4 0 Error messages to PROFIBUS standard 00001 Short circuit 00010 Undervoltage Supply voltage 00011 Overvoltage Supply voltage 00100 Output Module is overloaded 00101 Temperature rise output Module 0...

Page 61: ...e are module specific and are described with the according module If there is a diagnostic event for channel group 0 of a module there may be a module error as well as a channel error The entry is mad...

Page 62: ...x 7 Bit 5 0 reserved Bit 6 Hardware interrupt lost Bit 7 reserved x 8 Channel type 70h Module with digital inputs 71h Module with analog inputs 72h Module with digital outputs 73h Module with analog o...

Reviews: