Chapter 4 Analog Input
Manual VIPA System SLIO
4-14
HB300E - SM - Rev. 09/38
In the following there are the measuring ranges with function-number listed,
which were supported by the analog module.
With FFh the corresponding channel is deactivated.
The formulas listed here allow you to transform an evaluated measuring
value (digital value) to a value assigned to the measuring range (analog
value) and vice versa.
Measuring range
(function number)
Current (I)
Decimal (D)
Hex
Range
Formulas for
calculation
23.52 32511
7EFFh
overrange
20mA
27648
6C00h
10mA
13824
3600h
0mA
0
0000h
nominal range
0 ... 20mA
Siemens S7 format
(31h)
-3.52 -4864
ED00h
underrange
20
27648
I
D
⋅
=
27648
20
⋅
=
D
I
25.00mA 20480
5000h
overrange
20mA
16384
4000h
10mA
8192
2000h
0mA
0
0000h
nominal range
0 ... 20mA
Siemens S5 format
(41h)
-4.00mA -3277
F333h
underrange
20
16384
I
D
⋅
=
16384
20
⋅
=
D
I
Measuring range
(function number)
Current (I)
Decimal (D)
Hex
Range
Formulas for
calculation
22.81 32511
7EFFh
overrange
20mA
27648
6C00h
12mA
13824
3600h
4mA
0
0000h
nominal range
4 ... 20mA
Siemens S7 format
(30h)
1.19mA -4864
ED00h
underrange
16
4
27648
−
⋅
=
I
D
4
27648
16
+
⋅
=
D
I
24.00mA 20480
5000h
overrange
20mA
16384
4000h
12mA
8192
2000h
4mA
0
0000h
nominal range
4 ... 20mA
Siemens S5 format
(40h)
0.8mA -3277
F333h
underrange
16
4
16384
−
⋅
=
I
D
4
16384
16
+
⋅
=
D
I
Function-number
channel x
Summary of Contents for 021-1BB00
Page 1: ...Manual VIPA System SLIO Signal modules SM Order No VIPA HB300E_SM Rev 09 38...
Page 2: ...L...
Page 6: ...Contents Manual VIPA System SLIO ii HB300E SM Rev 09 38...
Page 26: ...Chapter 1 Basics and Assembly Manual VIPA System SLIO 1 18 HB300E SM Rev 09 38...
Page 36: ...Chapter 2 Digital Input Manual VIPA System SLIO 2 10 HB300E SM Rev 09 38...
Page 44: ...Chapter 3 Digital Output Manual VIPA System SLIO 3 8 HB300E SM Rev 09 38...
Page 102: ...Chapter 5 Analog Output Manual VIPA System SLIO 5 24 HB300E SM Rev 09 38...