Document: LT0439 Vigilant
MX1-Au
Operator Manual
Issue 1.73
23 October 2018
Page 6-17
Test options for output points are:
OPON
F1
puts the point into the Operated state, after a confirmation
prompt.
RESET
F3
resets the point, including any latched states and turns
off any TestOp state.
P241.8.0 |
Ancillary Relay 1 | DISABLE
| RESET
TestOp |
Fig 6-26 – Output Point - Test in Progress
While the Operate Test is active, the test options are:
DISABLE
F2
will disable the point. If the point is already disabled
this option will be
ENABLE
F2
.
RESET
F3
resets the point (stopping the test), including any latched
states.
The point is not automatically disabled by this test, so testing
some outputs may activate external equipment such as
sounders, door releases or even fire suppression equipment.
Also, at most 10 detector LEDs can be turned on at the same
time. Testing more than 10 simultaneously will still pass, just
the LED will not turn on.
MX1
translates sensor readings into analogue values. These values are
processed by algorithms to determine the status of the point. The raw
values, equivalent levels measured in physical units (for example, ppm
CO,
o
C Temperature, % Obscuration, % Alarm) and algorithms for a
point can be recalled on the display.
These are intended for device fault or performance diagnosis, and are
not very meaningful without a good understanding of the system.
From the Recall Point Status display, press
MENU
or
MENU
F4
:
Fig 6-27 – Recall Point Status Display
Using Point
Value Data
Viewing Point Values and Settings
Displaying
Point Values
P
1
.
32
.
1 814
CH CO
|
RESET
Shop
|
DISABLE
Normal
|
TEST
|
VALUES