Zones 1 to 3 | ALL
F1 enables all in range |
F4 enables normal in range |
| NORMAL
Fig 6-19 – Choice for Enabling A Range Of Zones
Selecting
ALL
F1
will enable all zones in the range, irrespective of their
status.
If any of these zones are in Alarm or Fault states, they will
resume their programmed behaviour in activating alarm
devices and fault outputs once they have been enabled.
If
NORMAL
F4
is selected, only those zones in the range that are in the
normal state will be enabled. Since (dependant on the configuration in
use) enabling zones in alarm could activate remote signalling, alarm
devices, etc., this option permits the system to be returned to service
without accidentally enabling an alarm and perhaps signalling the
brigade.
In the confirmation display press
OK
to enable the zones in the range, or
CANCEL
to abort the command.
Attempting to enable a zone that has all of its points
disabled will not work even though it falls within the
specified range of zones. To enable the zone, one or
more of its points will need to be enabled first.
From the recall zone status display, press
MENU
or
MENU
F4
to display
the menu options, then press
TEST
F3
to display the zone test menu.
Alternatively, from the base display press
TESTS
,
INITIATE
F4
,
ZONE
F1
and enter the zone number.
Zone 001 Std Detection G1 |ALRM TST
Office | OPERATE
Normal |AUTO RST
| FLT TST
Fig 6-20 – Zone Test Status and Menu
Testing Zones