Document: LT0439 Vigilant
MX1-Au
Operator Manual
Issue 1.73
23 October 2018
Page 6-7
From the base display, press
DISABLE
, then
POINT
F2
.
Do not press the f.b.p.
DISABLE
control when the Alarm List
is being shown unless the intent is to disable all alarms.
Disable Point | -TO-
: |
Enter E.D.S for single point |
or E.D.S F1 E.D.S for range | <-
Fig 6-10 – Point Number Entry Display – Disable Points
Enter the first point in the range, then
F1
followed by the last point in the
range.
Point numbering is described in “Point Numbers” on page 1-13.
Note that the selected range cannot span equipment numbers. If the
starting point is a device number then the end point must be another
device on the same equipment number. If the starting point number
includes a sub-point, then the end point must include a sub-point of the
same device. After pressing the
-to-
F1
key, the end point entry is
automatically configured to the allowed range.
F4
can be used to backspace to correct wrong entries.
Press
OK
.
If no configured points exist in the entered range, “No Valid
Points Selected” is shown briefly before the point number entry display
(Fig 6-10) is re-displayed.
P1.1.2-1.1.3 | DISABLE
2 disabled |
0 enabled |
Select command or CANCEL | ENABLE
Fig 6-11 – Point Disable/Enable Menu
Fig 6-11 shows the number of configured points in the range that are
already disabled and enabled.
Press
F1
to disable the range of points, or
F4
to enable the range of
points. A confirmation display will be shown.
Disabling or
Enabling a
range of Points