If
MENU
is pressed when the alarm list is displayed, the following menu
is shown.
Z003-Shop |MOREINFO
P1.32-Shop |PREV ALM
Z001-Office |MOREINFO
P1.1-Office |TECHMENU
Fig 2-3 – Example of Alarm Display Showing Menu
From the alarm list,
F1
to
F4
may be pressed for the
corresponding functions without first pressing
MENU
.
Pressing
TECHMENU
F4
allows access to all the other
menu functions while an alarm is present. Pressing and
holding CANCEL returns to the alarm list.
Pressing
MORE INFO
F1
or
MORE INFO
F3
will show the Alarm
Detail display for the particular alarm.
Shop |MOREINFO
Z003 P1.32.1 CO | PREV
Shopwindow | NEXT
CL: 1 ppm Alarm 1 of 3|ALRM LST
Fig 2-4 – Alarm Detail Display
NOTE
if the panel sending the alarm is not an
MX1
panel then the
information shown depends on the configuration of the sending panel.
For MX1 panels
The first line shows the zone name.
The second line shows the zone number, the point number (device
number and subpoint) and alarm type for the subpoint that caused the
alarm.
The third line shows the point name.
The fourth line shows the current level
(CL=”current analogue level”) in
appropriate units for the device type, in this case, parts per million of
carbon monoxide. It also states which alarm of the total number of
alarms this is.
Press
MORE INFO
F1
to show pre-programmed action text for the zone
and the date and time of the alarm.
NEXT
or
NEXT
F3
to step to the next (later) zone in alarm.
PREV
F2
key to step to the previous (earlier) alarm.
ALRM LST
F4
to return to the Fire Brigade Panel alarm list.
Viewing Alarm
Details