The following tables list the default Point text and a description of all the
in-built points. Some
MX1
configurations may have these points
changed or deleted.
Point Number Point Text Description
241.1
ALARM
DEVICES
This point indicates the Alarm Devices status and is used to
enable/disable the Alarm Devices. "Alarm Devices" are devices
(e.g. sounders and sirens) that operate to signal to building
occupants that a fire is present and the area should be
evacuated. The state of the Alarm Devices is controlled by output
logic, such that it is operated when there is an alarm on a non-
disabled zone that is mapped to the Alarm Devices.
241.2
GPIN1
Provides the status of the G.P IN 1 input (J2-1).
241.3
GPIN2
Provides the status of the G.P IN 2 input (J2-2).
241.4
GPOUT1
GPOUT1 is an open collector output (J7-1) with supervision
capability. The Operate state of the output can be controlled by
system or user logic. If supervision has been enabled in the
configuration then the Fault state is determined and shown by
the supervision input point GPOUT1S.
241.5
GPOUT1S
GPOUT1S is the supervision point for GPOUT1. If supervision is
enabled on GPOUT1 then the Fault state of the output will show
on this point. If GPOUT1 is not used then this point can be used
as an input.
241.6
GPOUT2
GPOUT2 is an open collector output (J7-2) with supervision
capability. The Operate state of the output can be controlled by
system or user logic. If supervision has been enabled in the
configuration then the Fault state is determined and shown by
the supervision input point GPOUT2S.
241.7
GPOUT2S
GPOUT2S is the supervision point for GPOUT2. If supervision is
enabled on GPOUT2 then the Fault state of the output will show
on this point. If GPOUT2 is not used then this point can be used
as an input.
241.8
ANC1
ANC1 is an ancillary relay with supervision capability (J4). The
Operate state of the point can be controlled by system or user
logic to energise the relay. If supervision has been enabled in the
configuration then the Fault state is determined and shown by
the ANC1S (241.9) point.
241.9
ANC1S
ANC1S is the supervision input (J4-5) for ancillary relay 1. If
supervision is enabled on ANC1 then the Fault state of the
output will show on this point. If supervision is not enabled on
ANC1 then ANC1S is a clean contact input with states
determined by the configuration.
241.10
ANC2
ANC2 is an ancillary relay with supervision capability (J5). The
Operate state of the point can be controlled by system or user
logic to energise the relay. If supervision has been enabled in the
configuration then the Fault state is determined and shown by
the ANC2S (241.11) point.
241.11
ANC2S
ANC2S is the supervision input (J5-5) for ancillary relay 2. If
supervision is enabled on ANC2 then the Fault state of the
output will show on this point. If supervision is not enabled on
ANC2 then ANC2S is a clean contact input with states
determined by the configuration.
Equipment Point Descriptions
Equipment 241
– MX1
Controller