50
1.
Turn ON the system ON/OFF switch on the control
unit.
The commissioning assistant starts automatically.
Note
When the appliance is initially started up, the dis-
play is in German.
Fig. 33
2.
Make required settings:
■
"Language"
■
"Date and time"
■
"Energy cockpit"
3. Only for multi boiler systems:
Tap
"Application"
.
Select
"Boiler in the Cascade"
.
4.
Use
to confirm.
The
"Commissioning"
menu reappears.
5.
Use
to confirm.
6.
Use
to confirm and adapt key parameters to the
system, e.g.
"Gas type"
.
or
Use to end commissioning. The system is oper-
ated with the factory settings.
Note
All parameters can be subsequently updated: See
from page 56.
7.
Use
to confirm.
8.
Use
to end commissioning.
Note
If commissioning was unsuccessful, an error mes-
sage appears.
Repeating commissioning
Note
Required only where control unit application is to be
changed.
Tap the following buttons:
1.
2. "Service"
3.
Enter the password "viservice".
4. "Commissioning"
Required parameters
Check parameter "01" in the
"General"
group and set
according to the following table:
Function
Single boiler system:
"Single boiler constant con-
trol"
Multi boiler system:
"Boiler in the Cascade"
Without external hook-up
Parameter "01:1"
—
Hook-up via
■
Plug
aVD
/
aVH
or
■
EA1 extension
Parameter "01:1"
Parameter "01:3"
Hook-up via Vitogate 300
Parameter "01:1"
Parameter "01:2"
Check all parameters in
Parameter level 1
and adjust
if required.
Check the following parameters in
Parameter level 2
and set according to requirements:
Commissioning
Commissioning the system
5863679
Commissioning