background image

Installation instructions

for contractors

VIESMANN

Vitoplex 100
Type PV1

, 150 to 620 kW

Oil/gas boiler

VITOPLEX 100

5592 753 GB

10/2014

Dispose after installation.

Summary of Contents for Vitoplex 100 PV1

Page 1: ...Installation instructions for contractors VIESMANN Vitoplex 100 Type PV1 150 to 620 kW Oil gas boiler VITOPLEX 100 5592 753 GB 10 2014 Dispose after installation...

Page 2: ...n Regulations Observe the following when working on this system Statutory regulations regarding the prevention of accidents Statutory regulations regarding environmental pro tection The Code of Practi...

Page 3: ...7 Making connections on the flue gas side 8 Fitting the thermal insulation 8 Boiler body thermal insulation 8 Rear thermal insulation 9 Side panels and burner cables 10 Front panel 11 Rear panels 11 P...

Page 4: ...ial usage for a purpose other than the heating up of heating water shall be deemed inappropriate Intended use presupposes that a fixed installation in conjunction with permissible components designed...

Page 5: ...utput kW 150 200 250 310 400 410 500 620 Anti vibration boiler supports Permissible load kg 1500 2700 3336 c front number mm pce 375 2 334 2 500 2 c back number mm pce 375 2 334 2 334 2 d mm 30 100 10...

Page 6: ...iler support can temporarily be overloaded To aid installation support the boiler on 3 x timbers 35 mm Changing the boiler door opening A A B C C D B Fig 4 Note The boiler door is hung on the opposite...

Page 7: ...ndicator According to EN 12828 a low water indicator can be omitted for Vitoplex 100 boilers up to 300 kW except in attic heating centres as the standard boiler control unit prevents impermissible hea...

Page 8: ...78 mm 250 and 310 kW 198 mm 400 to 620 kW 248 mm 2 Create a test port 3 Seal in and insulate the flue pipe Joints must be gas tight Fitting the thermal insulation Note All components required for fitt...

Page 9: ...and keep safe This will be required later Rear thermal insulation 2 1 Fig 8 Note Check that the serial number on the type plate matches the serial number stamped into the back panel of the boiler Fit...

Page 10: ...Note Provide burner cables on site if they are not supplied The inclusion of burner cables in the standard delivery depends on which control unit is being supplied Note Route the burner cables fA and...

Page 11: ...11 Front panel 2 3 9 x 9 5 2 3 9 x 9 5 3 1 Fig 10 Rear panels 3 9 x 9 5 3 9 x 9 5 2 1 Fig 11 Fitting the thermal insulation cont 5592 753 GB...

Page 12: ...ter temperature sensor as far as they will go into the sensor wells Power supply plug f is supplied with the control unit Please note Damaged capillary tubes will result in faulty sen sor function Nev...

Page 13: ...13 Top panels and type plate A B 3 9 x 9 5 4 2 3 1 5 3 9 x 9 5 3 9 x 30 Fig 14 A Boiler type plate Fitting the thermal insulation cont 5592 753 GB...

Page 14: ...ude from the thermal insu lation of the boiler door To safeguard perfect operation maintain the required minimum flame tube length After mounting the burner seal the annular gap between the flame tube...

Page 15: ...rtial load 60 C 155 Product ID CE 0085BP0365 Efficiency at 100 of the rated heating output 80 65 C 90 8 91 0 90 9 91 0 90 9 90 9 91 0 91 1 30 of the rated heating output 80 65 C 94 5 94 9 94 7 95 0 94...

Page 16: ...ropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com Viessmann Werke GmbH Co KG D 35107 Allendorf Telephone 49 6452 70 0 Fax 49 6452 70 2780 www viessmann com 5...

Reviews: