50
Parameter ad-
dress "B5":
Heating circuit pump "OFF"
Heating circuit pump "ON"
Summer eco function active
Summer economy function passive
1
RT
actual
>
RT
set
+ 5 K
RT
actual
< RT
set
+ 4 K
2
RT
actual
>
RT
set
+ 4 K
RT
actual
< RT
set
+ 3 K
3
RT
actual
>
RT
set
+ 3 K
RT
actual
< RT
set
+ 2 K
4
RT
actual
>
RT
set
+ 2 K
RT
actual
< RT
set
+ 1 K
5
RT
actual
>
RT
set
+ 1 K
RT
actual
< RT
set
6
RT
actual
>
RT
set
RT
actual
< RT
set
−
1 K
7
RT
actual
>
RT
set
−
1 K
RT
actual
< RT
set
−
2 K
8
RT
actual
>
RT
set
−
2 K
RT
actual
< RT
set
−
3 K
Coding in the delivered condition
Possible change
Flow temperature minimum limit
C5:20
Minimum flow temperature limit set
to 20 °C
C5:1
to
C5:100
Adjustable from 1 to 100 °C
Flow temperature maximum limit
C6:75
Maximum flow temperature limit
set to 75 °C
C6:10
to
C6:100
Adjustable from 10 to 100 °C
Room sensor limit
C8:31
Is available if code
"A0:1"
or
"A0:2"
and
"B0:1"
,
"B0:2"
or
"B0:3"
, heating group, are set.
No limit for room influence.
C8:1
to
C8:30
Room influence limit adjustable from
1 to 30 °C
Party mode time limit
F2:8
Party mode time limit is 8 h
F2:0
No time limit for party mode. Party
mode is deactivated when changing
the operating program to
"Heating"
.
F2:1
to
F2:12
Time limit adjustable from 1 to 12 h
Dissipate heat
F3:1
The "Dissipate heat" function regu-
lates the heating circuit flow tem-
perature to the set maximum (code
"C6"
, heating group).
F3:0
The
"Dissipate heat"
function is de-
activated for the selected heating
circuit.
Runtime set
F4:140
The mixer motor runs for 140 s for
the selected heating circuit.
F4:15
to
F4:255
Adjustable value in s
Codes
Code 1
(cont.)
5777 985 GB
Codes