30
Note
The same subscriber number must
not
be allocated
twice within the LON.
Only one Vitotronic
may be programmed as fault
manager.
All coding addresses in the table are listed in the "General" group.
Boiler control unit
Vitotronic 200-H
Vitotronic 200-H
LON
LON
Subscriber no. 1
Code "77:1"
Subscriber no. 10
Code "77:10"
Subscriber no. 11
Set
code "77:11".
Control unit is fault manager.
Code "79:1"
Control unit is not fault manager.
Code "79:0"
Control unit is not fault manager.
Code "79:0"
Control unit transmits the time.
Code "7b:1"
Control unit receives the time.
Set
code "81:3".
Control unit receives the time.
Set
code "81:3".
Control unit transmits outside tem-
perature.
Set
code "97:2".
Control unit receives outside tem-
perature.
Set
code "97:1".
Control unit receives outside temper-
ature.
Set
code "97:1".
Viessmann system number.
Code "98:1"
Viessmann system number.
Code "98:1"
Viessmann system number.
Code "98:1"
LON subscriber fault monitoring.
Code "9C:20"
LON subscriber fault monitoring.
Code "9C:20"
LON subscriber fault monitoring.
Code "9C:20"
Carrying out a LON subscriber check
The subscriber check is used to test communication
with the system devices connected to the fault man-
ager.
Requirements:
■
The control unit must be programmed as
fault man-
ager
(code "79:1" in the
"General"
group).
■
The LON subscriber number must be programmed in
all control units.
■
The LON subscriber list in the fault manager must be
up to date.
Service menu:
1. Press
OK
and
simultaneously for approx. 4 s.
2.
"Service functions"
3.
"Subscriber check"
4. Select subscriber (e.g. subscriber 10).
5. Start the subscriber check with
"OK"
.
■
Successfully checked subscribers are designated
with
"OK"
.
■
Unsuccessfully checked subscribers are identified
with
"Not OK"
.
Note
To perform another subscriber check:
Create a new subscriber list with
"Delete list?"
(sub-
scriber list is updated).
Note
During the subscriber check, the display of the relevant
subscriber shows the subscriber no. and
"Wink"
for
approx. 1 min.
Commissioning, inspection, maintenance
Connecting the control unit to the LON
(cont.)