20
3.
Replace any damaged components. Use new gas-
kets.
Note
Observe the positioning aid on the thermal insula-
tion block.
4.
Reassemble in reverse order. Observe torque val-
ues, see table on page 21.
Check the burner gauze assembly for damage. In the
event of damage, replace the burner gauze assembly.
A
B
C
D
E
F
G
4x
H
Fig. 12
200 to 318 kW
A
Ignition and ionisation electrodes
B
Burner gauze assembly gasket
C
Insulation mat
D
Burner door gasket
E
Thermal insulation block
F
Burner gauze assembly
G
Fan
H
Venturi extension, only for open flue operation
1.
Remove electrodes.
Commissioning, inspection, maintenance
Checking the burner gauze assembly and thermal…
(cont.)
5792 925 GB