
33
Changing the slope and level
A
B
Boiler water or flow temperature in °C
90
+20
-20
Outside temperature in °C
3.5
1.4
0.2
A
Changing the slope
B
Changing the level (vertical parallel
offset of the heating curve)
1. Slope:
Change with coding address "d3" in
code 1.
Setting range 2 to 35 (equals slope
0.2 to 3.5).
2. Level:
Change with coding address "d4" in
code 1.
Setting range -13 to
+
40 K.
Adjusting the set room temperature
Standard room temperature
90
-20
26 + 20
A
C
D
E
B
Example 1: Adjustment of standard room
temperature from 20 to 26
°
C
A
Boiler water temperature or flow
temperature in
°
C
B
Outside temperature in
°
C
C
Set room temperature in
°
C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Press the following keys:
1.
a
"1
r
" flashes.
2.
d
to select heating circuit A1 (heat-
ing circuit without mixer)
or
3.
a
"2
r
" flashes.
4.
d
to select heating circuit with
mixer M2.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5692 760 GB
Summary of Contents for VITOCONTROL-S, WB2B
Page 5: ...5 Keyword index 119 Index Index cont 5692 760 GB ...
Page 121: ...121 5692 760 GB ...
Page 122: ...122 5692 760 GB ...
Page 123: ...123 5692 760 GB ...