
VITOCELL 200-V
With a Vitodens system boiler the cylinder
is controlled by the built-in diverter valve and
the optional tank sensor and comes supplied
with all cold and hot water controls and a
two-port valve for domestic hot water.
The single coil cylinders are available in
seven sizes, from 90 litres to 300 litres.
Manufactured from the very latest high
specification Duplex stainless steel to resist
all forms of corrosion, the cylinders are
nevertheless light and easy to handle and
insulated with at least 50 mm of polyurethane
foam. This results in astonishingly low levels
of heat loss and a performance greater than
CHESS requirements.
All cylinders are also provided with an
auxiliary back up 3 kW electric immersion
heater. The operating thermostat and energy
cut-out are for use with non-Viessmann
boilers or traditional 'S' or 'Y' plan systems.
The immersion heater is fitted at the front
for easy access and designed for use in
un-vented installations, and it contains an
additional safety overheat thermostat.
The Vitocell 200 range of unvented hot water storage cylinders are indirectly heated
cylinders designed for use with Vitodens system boilers (or UK standard boilers).
CFC/HCFC free fire retardant polyurethane
foam with an ozone depletion potential
of zero (ODP Zero) and a global warming
potential (GWP) of one
Insulation exceeds CHESS Best Practice,
as low as 1.4 kW/24 hr
High recovery heating coil in less than
19 minutes
All cylinders have a separate sensor
pocket for connection to a Viessmann
4-pipe system
Stand alone cylinder, complies with G3
Building Regulations
High flow rates achievable working at
3.0 Bar
External expansion vessel (supplied)
Dimensions of 600 mm at widest point
Simple front connection compression
fittings
Back up 3 kW immersion heater
Simple maintenance – no anode required
Lightweight design for ease of transport
and handling
25 year warranty against corrosion
DHW heating in
conjunction with boilers
Vitocell 200-V
Model
200-V 90
732
550
16.5
19
0.90
12 litre 7160768
200-V 120
920
550
18
19
1.00
12 litre 7160769
200-V 150
1 107
550
18.5
19
1.20
18 litre 7160770
200-V 180
1 295
550
19
21
1.40
18 litre 7160771
200-V 210
1 493
550
20.5
26
1.60
24 litre 7160772
200-V 250
1 733
550
21.5
30
1.75
24 litre 7160773
200-V 300
2 020
550
25
32
1.83
40 litre 7160774
Height
(mm)
Diameter
(mm)
kW rating of
primary coil (kW)
Part no.
Recovery time after
70% draw of (min)*
Stand-by losses
(kWh/24h)**
Expansion
vessel
* Approx re-heat time for 70% of cylinder contents from 15°C to 65°C using a 82°C flow
** Meets CHESS Best practice requirements
Vitocell 200-V
Summary of Contents for Vitocell 200-B
Page 48: ...Training ...