58
Parameters for solar DHW heating
Parameters in conjunction with solar control module type SM1
Setting
"Solar"
Ó
"Type solar control unit 7A00"
"3"
Parameter C0xx
See installation and service instruc-
tions for "Solar control module, type
SM1".
Parameters for instantaneous heating water heater
Parameter
Setting
"Electr booster heater"
Ó
"Enable instantaneous heating water heater 7900"
"1"
"Output for instant. heating water heater at power-OFF 790A" "1"
3 kW
"2"
6 kW
"3"
9 kW
!
Please note
After the value
"1"
has been set for
"Enable
instantaneous heating water heater 7900"
,
the prompt
"Secondary circuit filled?"
auto-
matically appears. If this prompt is responded to
with
"No"
, the instantaneous heating water
heater will not be enabled. Set
"Enable instan-
taneous heating water heater 7900"
to
"2"
.
Fill the secondary circuit. Confirm prompt
"Sec-
ondary circuit filled?"
with
"Yes"
.
Enable instantaneous heating water heater for DHW heating
Parameter
Setting
"DHW"
Ó
"Enable electric heaters for DHW heating 6015"
"1"
Parameters for external heat generators
Parameter
Setting
"External heat source"
Ó
"Enable external heat source 7B00"
"1"
Enable external heat source for DHW heating
Parameter
Setting
"External heat source"
Ó
"Enable external heat source for DHW heating 7B0D"
"1"
Parameters for immersion heater
Parameters
Setting
"DHW"
Ó
"Enable electric heaters for DHW heating 6015"
"1"
"Enable booster heaters for DHW heating 6014"
"1"
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5855006