58
Cooling function parameters
Parameter
Setting
"Cooling"
Ó
"Cooling function 7100"
"0"
No cooling
"1"
Natural cooling with NC-Box with-
out mixer (accessory)
"2"
Natural cooling with NC-Box with
mixer (accessory)
"3"
"Active cooling"
"Cooling circuit 7101"
"1"
Heating circuit A1/HC1
"2"
Heating circuit M2/HC2
"3"
Heating circuit M3/HC3
"4"
Separate cooling circuit SKK
Room temperature sensor for separate cooling circuit
Parameter
Setting
"Cooling"
Ó
"Ranking room temp sensor separate cooling circuit 7106"
"0"
Connection F16
"1"
Heating circuit A1/HC1
"2"
Heating circuit M2/HC2
"3"
Heating circuit M3/HC3
"4"
Do not adjust.
Parameters for ice store system
Parameter
Setting
"System definition"
Ó
"Select primary source 7030"
"1"
"External extension 7010"
"2"
Parameter
Setting
"Solar"
Ó
"Type solar control unit 7A00"
"2"
Possibly set additional parameters.
Parameter
Setting
"System definition"
Ó
"Start hysteresis solar air absorber 7031"
"0"
to
"500"
(
≙
0 to 50 K)
"Min. runtime to suppress summer mode 7035"
"0"
to
"1440"
min
"Last calendar week for summer mode 7036"
Calendar week
"1"
to
"53"
Parameters for utilisation of power generated on site
Parameter
Setting
"Photovoltaics"
Ó
"Enable own energy consumption PV 7E00"
"1"
"Threshold for electrical power 7E04"
"0"
to
"300"
(
≙
0 to 30 kW)
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5838144