57
External blocking of compressor and pumps
Parameter
Setting
"System definition"
Ó
"Effect of external blocking on pumps/compressor 701A"
"0"
to
"31"
External blocking of the compressor; mixer in control mode or CLOSED
Parameter
Setting
"System definition"
Ó
"Effect of ext. blocking on heat pump/heating circuits 7015"
"0"
to
"8"
"Effect of external blocking on pumps/compressor 701A"
"0"
to
"31"
Parameters for instantaneous heating water heater
Parameter
Setting
"Electr booster heater"
Ó
"Enable instantaneous heating water heater 7900"
"1"
"Output for instant. heating water heater at power-OFF 790A" "1"
3 kW
"2"
6 kW
"3"
9 kW
Enable instantaneous heating water heater for DHW heating
Parameter
Setting
"DHW"
Ó
"Enable electric heaters for DHW heating 6015"
"1"
Parameters for external heat generators
Parameter
Setting
"External heat source"
Ó
"Enable external heat source 7B00"
"1"
Enable external heat source for DHW heating
Parameter
Setting
"External heat source"
Ó
"Enable external heat source for DHW heating 7B0D"
"1"
Parameters for swimming pool water heating
Parameter
Setting
"System definition"
Ó
"External extension 7010"
"1"
or
"3"
"Swimming pool 7008"
"1"
Parameters for solar DHW heating
Parameters in conjunction with solar control module type SM1
Setting
"Solar"
Ó
"Type solar control unit 7A00"
"3"
Parameter C0xx
See installation and service instruc-
tions for "Solar control module, type
SM1".
Commissioning, inspection, maintenance
Commissioning the system
(cont.)