3.2 Specification
Specification
230 V appliances
Type AWOT-M-E/AWOT-M-E-AC
221.A04
221.A06
221.A08
221.A10
221.A13
221.A16
Heating performance data
to EN 14511
(A2/W35)
Rated heating output
kW
2.61
3.11
4.04
5.01
5.92
6.47
Fan speed
rpm
600
600
650
600
600
600
Power consumption
kW
0.73
0.82
1.02
1.27
1.48
1.79
Coefficient of performance ε (COP) in
heating mode
3.57
3.78
3.96
3.96
4.01
3.61
Output control
kW
2.00 to 4.10 2.40 to 5.50 2.80 to 7.00 4.40 to 9.60
4.80 to
10.20
5.20 to
10.70
Heating performance data
to EN 14511
(A7/W35, 5 K spread)
Rated heating output
kW
3.96
4.83
5.62
7.01
7.85
8.64
Fan speed
rpm
600
600
650
600
600
600
Air flow rate
m
3
/h
2250
2250
2600
4500
4500
4500
Power consumption
kW
0.87
1.02
1.19
1.49
1.66
1.90
Coefficient of performance ε (COP) in
heating mode
4.56
4.72
4.71
4.69
4.72
4.54
Output control
kW
2.44 to 4.18 3.00 to 6.00 3.47 to 7.54
5.48 to
12.60
6.00 to
13.70
6.42 to
14.30
Heating performance data
to EN 14511
(A–7/W35)
Rated heating output
kW
3.81
5.70
6.67
8.69
9.50
11.03
Power consumption
kW
1.31
1.96
2.31
2.77
3.09
3.90
Coefficient of performance ε (COP) in
heating mode
2.91
2.91
2.89
3.14
3.07
2.83
Heating performance data
to EN 14511
(A35/W7)
Rated cooling capacity
kW
2.00
3.00
4.00
5.00
6.00
7.00
Fan speed
rpm
600
600
650
900
900
900
Power consumption
kW
0.80
1.20
1.40
1.90
2.30
2.70
Energy efficiency ratio EER in cooling
mode
2.40
2.60
2.90
2.70
2.65
2.60
Output control
kW
Up to 3.90
Up to 4.90
Up to 6.20
Up to 8.00
Up to 9.00
Up to 10.30
Heating performance data
to EN 14511
(A35/W18)
Rated cooling capacity
kW
4.00
5.00
6.00
7.00
8.20
9.20
Fan speed
rpm
600
600
650
900
900
900
Power consumption
kW
0.80
1.35
1.40
1.67
2.08
2.42
Energy efficiency ratio EER in cooling
mode
4.20
4.20
4.30
4.10
3.95
3.80
Output control
kW
Up to 5.00
Up to 6.00
Up to 7.00
Up to 11.00 Up to 12.50
Up to 13.90
Air intake temperature
Cooling mode (type AWOT-M-E-AC only)
– Min.
°C
10
10
10
10
10
10
– Max.
°C
45
45
45
45
45
45
Heating mode
– Min.
°C
–20
–20
–20
–20
–20
–20
– Max.
°C
35
35
35
35
35
35
Heating water
(secondary circuit)
Minimum flow rate
l/h
700
700
700
1550
1550
1550
Minimum volume in the heating system,
cannot be fitted with shut-off devices
l
50/40
*5
50/40
*5
50/40
*5
50/40
*5
50/40
*5
50/40
*5
Max. external pressure drop (RFH) at
minimum flow rate
mbar
705
705
705
400
400
400
kPa
70.5
70.5
70.5
40
40
40
Max. flow temperature
°C
60
60
60
60
60
60
Outdoor unit electrical values
Rated voltage, compressor
1/N/PE 230 V/50 Hz
Max. operating current, compressor
A
13.0
14.6
14.6
19.9
23.3
23.3
Cos φ
0.99
0.99
0.99
0.99
0.99
0.99
Starting current, compressor
A
15
15
15
15
15
15
Fuse rating
B16 A
B16 A
B16 A
B25 A
B25 A
B25 A
IP rating
IP X4
IP X4
IP X4
IP X4
IP X4
IP X4
*5
When using the heating water buffer cylinder Vitocell 100-E, type SVPA, part no. ZK03801 in the secondary circuit return