72
Room temperature sensor for separate cooling circuit
Parameter
Setting
"Cooling"
Ó
"Ranking room temp sensor separate cooling circuit 7106"
"0"
Connection F16
"1"
Heating circuit HC1
"2"
Heating circuit HC2
"3"
Heating circuit HC3
"4"
Do not adjust.
Cooling function in systems with a heating water/coolant buffer cylinder
Parameter
Setting
"Cooling"
Ó
"Cooling function 7100"
"3"
"Buffer cylinder"
Ó
"Enable buffer cylinder/low loss header 7200"
"2"
"Heating circuit 1"
/
"Heating circuit 2"
/
"Heating circuit 3"
Ó
"Cooling 2030"
and/or
"Cooling 3030"
and/or
"Cooling 4030"
"2"
Parameters for solar DHW heating
Parameters in conjunction with solar control module type SM1
Setting
"Solar"
Ó
"Type solar control unit 7A00"
"3"
Parameter C0xx
See installation and service instruc-
tions for "Solar control module, type
SM1".
Parameters for instantaneous heating water heater
Parameter
Setting
"Electr booster heater"
Ó
"Enable instantaneous heating water heater 7900"
"1"
"Output for instant. heating water heater at power-OFF 790A" "1"
3 kW
"2"
6 kW
"3"
9 kW
!
Please note
After the value
"1"
has been set for
"Enable
instantaneous heating water heater 7900"
,
the prompt
"Secondary circuit filled?"
auto-
matically appears. If this prompt is responded to
with
"No"
, the instantaneous heating water
heater will not be enabled. Set
"Enable instan-
taneous heating water heater 7900"
to
"2"
.
Fill the secondary circuit. Confirm prompt
"Sec-
ondary circuit filled?"
with
"Yes"
.
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
6150148