60
!
Please note
If a casing door is not securely closed this can
lead to damage from condensation, vibrations
and excessive noise.
■
Seal the appliance so it is soundproof and dif-
fusion-proof.
■
On pipe and hose outlets, ensure the thermal
insulation is seated correctly.
Danger
The absence of system component earthing can
lead to serious injury from electrical current and
component damage in the event of an electrical
fault.
Attach earth conductor to front panel and side
panel.
Indoor unit: Fitting the front panel
3.
2x
2.
1.
Fig. 57
3.
Ensure that the locking screws are tightened
before operating.
Outdoor unit: Fitting the side cover
In reverse order to "Opening the outdoor unit wiring
chamber": See page 25.
Installation sequence
Closing the heat pump
6150148
Installation