108
Coding in the delivered condition
Possible change
Cleaning blocking
63:0
Do not block
heat exchanger
cleaning of the boiler.
63:1
Blocking times for heat exchanger
cleaning from 22:00 to 06:00.
63:2
Blocking times for heat exchanger
cleaning from 21:00 to 07:00.
63:3
Blocking times for heat exchanger
cleaning from 20:00 to 08:00.
63:4
Blocking times for heat exchanger
cleaning from 19:00 to 09:00.
Primary air damper, maximum limit
82:...
Max. position of primary air damp-
er in % at full load
82:5
to
82:100
Setting range in %
Primary air damper, minimum limit
83:...
Min. position of primary air damper
in % at partial load
83:5
to
83:100
Setting range in %
Lambda probe, automatic system
F9:1
■
Automatic start of Lambda probe
heating
■
Calibration of Lambda probe
manual only
F9:0
■
Lambda probe heating always on
■
Calibration of Lambda probe man-
ual only
F9:2
■
Automatic start of Lambda probe
heating
■
Automatic calibration of Lambda
probe
O2 probe type
FF:0
Lambda probe used: Type LSM 11 FF:1
Lambda probe used: Type NGK
FF:2
0 to 20 mA
FF:3
Lambda probe used: Wideband
probe with BLS
Charging
Different codes will be available depending on the set
"Charging scheme"
.
Coding
Coding in the delivered condition
Possible change
Run feed until empty
05:1
Feed is run until empty.
05:0
Feed is
not
run until empty.
Terminate 'run feed until empty' at
17:16
Emptying of the feed is terminated
when the residual oxygen content
of the flue gas is 16 %.
17:10
to
17:20
Setting range in %
Feed screw conveyor temperature
18:70
Max. temperature of the feed
screw conveyor, 70 °C
18:20
to
18:250
Setting range in °C
Codes
Code 2
(cont.)
5679249
Codes