12
!
Please note
Incorrect handling can lead to irreparable dam-
age to the DHW heat pump.
■
Never
drill into the sheet steel casing of the
DHW heat pump.
■
Never
use the connectors as a transport aid.
■
Carefully remove the DHW heat pump from
the pallet. The EPS padding underneath can
be removed for this.
Align the DHW heat pump horizontally.
35
!
3x
Fig. 7
Conversion to outdoor air mode
Note
In outdoor air mode, at outside temperatures below 6 °C, the maximum DHW tem-
perature of 62 °C is not achieved in the operating programs
"ECO"
and
"SMART"
.
-5
30
0
10
20
30
40
50
60
70
Air intake temperature in °C
DHW temperature
in
°C
A
6
62
Fig. 8
A
Maximum DHW temperature achievable by the heat pump
Installation sequence
Siting the DHW heat pump
6136003