72
Fault code dis-
played
System characteristics
Cause
Measures
FA
Burner in a fault state
Fan idle state is not
reached.
Check fan, check connecting ca-
bles to fan.
Press reset button
R
.
Fb
Burner in a fault state
3 x flame blow-off during
operation
Check oil supply, check nozzle.
Press reset button
R
.
Fd
Burner in a fault state and ad-
ditional fault b7 is displayed
Solenoid coil faulty
Control unit faulty
Check solenoid coil by temporarily
replacing it.
Check coding address 38: if the
value is at 38:33, the control unit is
faulty.
Before replacing the control unit,
check while the control unit is
switched on to see if the green
LED on the ignition unit is flashing.
If the LED is not flashing, also re-
place the ignition unit.
Fd
Burner blocked
Burner control unit fault
Press reset button
R
. Replace con-
trol unit if fault persists.
FE
Burner blocked or in a fault
state
Boiler coding card or main
PCB faulty, or incorrect
boiler coding card
Press reset button
R
. If the fault
persists, check the boiler coding
card and replace boiler coding card
or control unit if necessary.
FF
Burner blocked
Internal fault
Restart the appliance. Replace the
control unit if the appliance will not
restart.