38
A
B
Boiler
water
or
flow temperature
in °C
90
+20
-20
Outside temperature in °C
3.5
1.4
0.2
Fig. 32
A
Changing the slope
B
Changing the level (vertical parallel offset of the
heating curve)
Extended menu:
1.
å
2.
"Heating"
3. Select heating circuit.
4.
"Heating curve"
5.
"Slope"
or
"Level"
6. Select heating curve according to the system
requirements.
Linking the control unit to the LON
The LON communication module must be plugged in.
Note
The data transfer via LON can take several minutes.
Example: Single boiler system with Vitotronic 200-
H and Vitocom 200
Set the LON subscriber numbers and further functions
via code 2 (see the following table).
Note
The same subscriber number must
not
be allocated
twice within the LON.
Only one Vitotronic
may be programmed as fault
manager.
All coding addresses in the table are listed in the "General" group.
Boiler control unit
Vitotronic 200-H
Vitotronic 200-H
Vitocom
LON
LON
LON
Subscriber no. 1
Code "77:1"
Subscriber no. 10
Code "77:10"
Subscriber no. 11
Set
code "77:11".
Subscriber no. 99
Control unit is fault manager.
Code "79:1"
Control unit is not fault man-
ager.
Code "79:0"
Control unit is not fault man-
ager.
Code "79:0"
Device is fault man-
ager.
Control unit transmits the
time.
Code "7b:1"
Control unit receives the
time.
Set
code "81:3".
Control unit receives the
time.
Set
code "81:3".
Device receives the
time.
Control unit sends outside
temperature.
Set
code "97:2".
Control unit receives outside
temperature.
Set
code "97:1".
Control unit receives outside
temperature.
Set
code "97:1".
—
Commissioning, inspection, maintenance
Adjusting the heating curves
(cont.)
5686 293 GB