8
"Vitovent 300-W" operating instructions
Setting the air flow rates
!
Please note
Incorrect settings can lead to operational disrup-
tions.
Settings must only be made/changed by a quali-
fied contractor.
Incorrect operation by system users will invalid-
ate the warranty.
Factory settings
Display
Ventilation stage
Vitovent 300-W for maximum air flow
rate
300 m
3
/h
400 m
3
/h
"Air Airflow 0"
Background ventilation (minimum
air flow rate)
50 m
3
/h
50 m
3
/h
"Air Airflow 1"
Reduced ventilation (reduced air
flow rate)
100 m
3
/h
100 m
3
/h
"Air Airflow 2"
Standard ventilation (standard air
flow rate)
150 m
3
/h
200 m
3
/h
"Air Airflow 3"
Intensive ventilation (maximum air
flow rate)
225 m
3
/h
300 m
3
/h
Setting ranges
Display
Ventilation stage
Vitovent 300-W for max. air flow rate
300 m
3
/h
400 m
3
/h
"Air Airflow 0"
Background ventilation (minimum
air flow rate)
Do not adjust
Do not adjust
"Air Airflow 1"
Reduced ventilation (reduced air
flow rate)
50
to
300 m
3
/h
50
to
400 m
3
/h
"Air Airflow 2"
Standard ventilation (standard air
flow rate)
50
to
300 m
3
/h
50
to
400 m
3
/h
"Air Airflow 3"
Intensive ventilation (maximum air
flow rate)
50
to
300 m
3
/h
50
to
400 m
3
/h
Commissioning, inspection, maintenance
Setting the language, time and date
5793 605 GB