36
Rated voltage
230 V
∼
Rated frequency
50 Hz
Rated current
2 A
Power consumption
5.5 W
Protection class
I
IP rating
IP 20 D to EN 60 529; ensure through
design/installation.
Permissible ambient temperature
■ During operation
0 to +40 °C
■ During storage and transport
–20 to +65 °C
Rated relay output breaking capacity
■ Heating circuit pump
1 A 230 V~
■ Mixer motor
0.1 A 230 V~
Flow temperature sensor/low loss header temperature sensor (separate
accessories)
Sensor type
NTC 10 kΩ, at 25 °C
IP rating
IP 53 to EN 60529; ensure through de-
sign/installation.
Permissible ambient temperature
■ Operation
0 to +120 °C
■ Storage and transport
−20 °C to +70 °C
Specification
5836498
Summary of Contents for Divicon
Page 9: ...9 Removing the thermal insulation 3 2 4 1 Preparing for installation 5836498 ...
Page 10: ...10 Fitting a single module without manifold 1 2 Ø 10 Wall mounting 5836498 ...
Page 11: ...11 1 2 A B A Heating flow B Heating return Wall mounting cont 5836498 ...
Page 17: ...17 Wall mounting cont 5836498 ...
Page 20: ...20 Low loss header if supplied 1 3 2 Fitting the thermal insulation 5836498 ...
Page 21: ...21 Manifold 1 2 Fitting the thermal insulation cont 5836498 ...
Page 25: ...25 2 3 1 4 Fitting the thermal insulation cont 5836498 ...
Page 39: ...39 5836498 ...