Gas type conversion (only for operation with LPG)
1
2
1. Only possible on appliances with
26 and 35 kW.
Set adjusting screw
A
on the gas
train to "2".
2.
Turn ON/OFF switch
8
ON.
3.
Select the gas type in coding address
"82".
■ Call up code 2.
■
"General"
■ In coding address "11", select
value "9".
■ In coding address "82", select
value "1" (LPG operation).
■ Set code "11" value unequal "9".
■ End service functions.
4.
Open the gas shut-off valve.
5.
Affix label "G31" (supplied with the
technical documentation) below the
type plate on the side panel.
Function sequence and possible faults
Display
Measures
Control unit
issues a heat
demand
no
Increase set value
and ensure heat is
drawn off
yes
Fan starts
no
After approx. 51 s
fault F9
Check the fan, fan
connecting cables,
power at the fan
and fan control
Commissioning, inspection, maintenance