Gas-fired condensing boiler

638 to 3361 MBH / 187 to 985 kW

Product may not be exactly as illustrated.

Vitocrossal 300, CT3 boiler with
Vitotronic NR2 control

Technical Data Manual

Model Nos. and pricing: see Price List

Vitocrossal 300

CT3 Series

High efficiency, gas-fired condensing boiler

for natural gas or liquid propane
with vertical Inox-Crossal heat exchanger surfaces
of corrosion-resistant stainless steel.
For operation without low limit on boiler return water
temperature.
For closed loop hot water heating systems with maximum
supply water temperatures of 210°F / 99°C for a
maximum operating pressure of 30 psig.

Heating input: 638 to 3361 MBH

187 to 985 kW

5285 871 v1.9 11/2012

Summary of Contents for CT3-22

Page 1: ...d pricing see Price List Vitocrossal 300 CT3 Series High efficiency gas fired condensing boiler for natural gas or liquid propane with vertical Inox Crossal heat exchanger surfaces of corrosion resistant stainless steel For operation without low limit on boiler return water temperature For closed loop hot water heating systems with maximum supply water temperatures of 210 F 99 C for a maximum oper...

Page 2: ...o return connections providing separate connection for heating circuits with lower return temperature This leads to increased hot gas condensation H Easy handling in boiler rooms through particularly low build height and weight also available in sections H Easy installation and elimination of wiring mistakes with Viessmann prewired plug in system H Heating boiler heating system control domestic ho...

Page 3: ...VITOCROSSAL 300 CT3 3 Two return Stainless steel Stainless steel Wide diameter Highly effective 4 connections arranged Inox Crossal heat water cooled water walls proper wrap around insulation above each other exchanger surfaces combustion chamber gravity circulation 5285 871 v1 9 ...

Page 4: ...of installed header v Width upper with jacketing w Width lower with jacketing Boiler support frame x Length y Width z Height inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm 59 1516 27 684 697 8 1773 64 1636 40 1016 797 8 2027 34 874 31 798 35 895 27 690 2 70 62 1594 27 684 71d 1808 67 1714 40 1016 81d 2062 34 874 31 798 38e 975 27 690 2...

Page 5: ...urn temperature of 140 F 60 C Mass flow rate of flue gas Gas volume of combustion chamber and heat exchanger F C F C F C lbs h kg h ft 3 m3 113 45 104 40 167 75 704 320 8 83 0 250 113 45 104 40 167 75 928 422 9 92 0 281 113 45 104 40 167 75 1179 536 12 00 0 340 113 45 104 40 167 75 1531 696 15 90 0 450 113 45 104 40 167 75 1903 865 18 40 0 521 113 45 104 40 167 75 2380 1082 21 54 0 610 113 45 104 ...

Page 6: ...1854 88 2254 9 200 8 241 36 921 7d 182 11 284 59 1500 7 190 3 79 45 1157 62 1573 39 990 4 100 29 751 12 325 22 577 73 1854 88 2254 9 200 8 241 36 921 7d 182 11 284 59 1500 7 190 3 79 51 1313 68 1727 39 990 4 100 29 755 14 363 25 644 80 2043 97 2463 10 250 11 280 38 965 87 8 225 14 360 63 1621 7 197 2 65 55 1405 76 1930 43 1092 4 100 29 755 14 363 25 644 80 2043 97 2463 10 250 11 280 38 965 87 8 22...

Page 7: ...vent high levels of humidity H Prevent freezing and ensure good ventilation Boiler model CT3 17 22 28 37 46 57 72 89 v w x y z inches mm inches mm inches mm inches mm inches mm 28 711 62 1593 36 930 40 1012 41 1048 28 711 65 1671 39 1000 40 1012 41 1048 28 711 69 1752 43 1100 40 1012 41 1048 35 889 72 1828 59 1500 44 1128 45 1149 35 889 75 1906 59 1500 44 1128 45 1149 39 991 81 2062 59 1500 44 112...

Page 8: ... 40 F t 11 C t 22 C t GPM GPM ltrs s ltrs s 61 31 3 9 2 0 81 41 5 1 2 6 103 52 6 5 3 3 134 67 8 5 4 2 166 83 10 5 5 3 208 104 13 2 6 6 260 130 16 5 8 2 323 162 20 4 10 3 t temperature difference This boiler does not require a flow switch 5285 871 v1 9 60 80 70 8 7 1 2 3 4 5 6 10 20 30 40 50 60 100 2 3 4 5 6 7 8 10 20 30 40 50 Flow rate Pressure drop 40 20 16 w c 8 8 13 2 17 6 22 26 4 44 88 132 176...

Page 9: ...otronic 300 type GW2 for modulating boiler water temperature with mixing valve control for a maximum of two heating circuits with mixing valve H with Vitocontrol control panel Vitotronic 100 type GC1 and Vitocontrol S CT3 control panel with Vitotronic 333 for outdoor reset mode and mixing valve control for a maximum of 2 heating circuits with mixing valve and additional Vitotronic 050 type HK1S or...

Page 10: ...el 905 662 6600 Fax 905 662 5352 Toll free 1 800 263 9308 Security Chimneys Division of Security Chimneys Ltd 2125 Monterey Laval PQ H7L 3T6 Tel 450 973 9999 Fax 450 973 2222 Toll free 1 800 667 3387 Van Packer Co Inc 302 Mill Street PO Box 307 Buda IL 61314 Tel 309 895 2311 Fax 309 895 3891 Toll free 1 888 877 8225 Exhausto CASV CASI Mechanical Draft System Wesmech Technical Sales 50 Ronson Drive...

Page 11: ...combustion air Exposing the boiler to pressures and tempratures higher than its certified rating See warranty sheet for details System layout The boiler water temperature limit is factory set to 167 F 75 C The boiler water temperature limit can be increased by altering the adjustable high limit to increase the supply water temperature To minimize piping losses of the system however Viessmann recom...

Page 12: ...ot a flue gas silencer is required can be predicted only with some difficulties because of the complexity of the creation and propagation of flame noise the interaction between the burner boiler and the flue gas system as well as the operating mode flue gas system operating with positive or negative pressure It is advisable therefore to assess the noise emission into the neighborhood and to consid...

Page 13: ...rner 2 Model WG30 WG30 G3 G3 G3 G5 G5 G7 Riello Burners 1 Boiler model CT3 17 22 28 37 46 57 72 89 Fully modulating burner 2 Model G750 G900 RS28 M RS38 M RS50 M RS50 M RS70 M RS100 M 1 Only the Weishaupt low NOx and standard head and Riello standard head burner models stated are CSA certified with the Vitocrossal boiler series as indicated on the boiler rating plate 2 Burners are available in 2 s...

Page 14: ...14 VITOCROSSAL 300 CT3 5285 871 v1 9 ...

Page 15: ...VITOCROSSAL 300 CT3 15 5285 871 v1 9 ...

Page 16: ...acturing Company U S Inc 45 Access Road Warwick Rhode Island 02886 USA 1 800 288 0667 Fax 401 732 0590 www viessmann us com info viessmann us com 16 VITOCROSSAL 300 CT3 Printed on environmentally friendly recycled and recyclable paper Printed on environmentally friendly recycled and recyclable paper 5285 871 v1 9 Technical information subject to change without notice ...