Draining gas condensing module on the heating water side
A
Fig. 92
1.
Shut off the connections on the heating water side.
2.
Attach a hose to drain valve
A
and connect to a
drain.
3.
Open drain valve
A
.
Draining the heating water buffer cylinder
Fig. 93
1.
Check that the fuel cell module is switched off.
2.
Connect the hose to the drain valve and route it
into a suitable container or drain outlet.
3.
Turn the lever on the drain valve to position
C
.
Note
This will not drain the process circuit of the fuel cell
module. See page 81.
Troubleshooting
Repairs (gas condensing module)
(cont.)