62
Commissioning without the commissioning assistant
Enabling the service menu
The service menu can be enabled from
any menu.
Press
OK
+
å
simultaneously for
approx. 4 s.
Disabling the service menu
The service menu remains active until it
is disabled with
"Terminate service?"
,
or if no operation takes place for 30
minutes.
Setting parameters using the "Sys-
tem scheme" example
To set a parameter, first select the
parameter group and then the parame-
ters.
All parameters are displayed as plain
text. A parameter code is also assigned
to each parameter.
Service menu:
1. Press
OK
+
å
simultaneously for
approx. 4 s
2. Select
"Coding level 1"
3. Select parameter group:
"System
definition"
4. Select parameter:
"System scheme
7000"
5. Set system scheme:
"6"
Alternatively, if the service menu was
already enabled:
Extended menu
1.
å
2.
"Service"
3. Select
"Coding level 1"
4. Select parameter group:
"System
definition"
5. Select parameter:
"System scheme"
6. Confirm parameter code:
"7000"
7. Set system scheme:
"6"
Required parameters for components connected on site
Detailed explanations regard-
ing the parameters
Service instructions for Vitotronic
200 heat pump control unit
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5601 574 GB
Summary of Contents for BWT 221.A06
Page 20: ...20 aCH 10 9 Installation sequence Siting the heat pump cont 5601 574 GB ...
Page 22: ...22 4x 18 21 4x 6x 20 2x 19 Installation sequence Siting the heat pump cont 5601 574 GB ...
Page 23: ...23 25 2x 24 4x 22 23 Installation sequence Siting the heat pump cont 5601 574 GB Installation ...
Page 28: ...28 4 1 3 2 Installation sequence Siting the heat pump cont 5601 574 GB ...
Page 71: ...71 Opening programming unit 2 2x 1 3 Troubleshooting Repairs cont 5601 574 GB Service ...
Page 122: ...122 5601 574 GB ...
Page 123: ...123 5601 574 GB ...