43
■
Only those actuators are shown that are installed
and can be controlled, according to system equip-
ment level.
■
Activating the actuator test switches all actuators to
zero volt.
■
Individual actuators can be started in succession in
this menu.
■
All actuators can be switched off simultaneously.
■
The actuator test stops automatically after
approx. 30 min or with .
1. Service menu:
Press
OK
+
å
simultaneously and hold for
approx. 4 s.
2. "Actuator test"
.
3.
Select required actuator.
4.
Set the required condition: See the following table.
5.
Use to call up the
"System overview"
and the
diagnostic page
"Refrigerant circ controller"
,
without
terminating the actuator test. Back to the
actuator test display with
OK
.
Component
Possible modes
Actuators without output-dependent control, e.g. compressor
"ON"
/
"OFF"
Electronic expansion valves
"AUTO"
/
"MIN"
/
"MAX"
"All actuators OFF"
All actuators are switched off simultaneously.
"Yes"
/
"No"
Actuator test
Actuator test (testing outputs)
5800 917 GB
Diagnosis