12
Installation room requirements
!
Please note
Unfavourable ambient conditions can lead to
malfunctions and appliance damage.
■
The installation room must be dry and free
from the risk of frost.
■
Ensure ambient temperatures between 0 and
35 °C.
Danger
Dust, gases and vapours can be damaging to
health and trigger explosions.
Avoid dust, gases and vapours in the installation
room.
!
Please note
Overloading the floor can result in damage to
the building structure.
Observe the permissible floor load. Take the
weight of the appliance into account.
Weight
Type
Weight in kg
BW 301.C090
770
BW 301.C120
870
BW 302.C090
720
BW 302.C110
910
BW 302.C140
1180
BW 302.C180
1280
BW 302.C230
1425
■
To prevent the transmission of structure-borne noise,
never site the appliance above ceilings with wooden
joists (e.g. in the attic).
■
Level the appliance horizontally.
Where floors are uneven, distribute the load evenly
across the adjustable feet.
■
Observe minimum room volume (to EN 378).
Note
Additional, country-specific regulations apply.
Minimum room volume, based on the available
air volume
Type
Minimum room volume
in m
3
BW 301.C090
36
BW 301.C120
40
BW 302.C090
34
BW 302.C110
38
BW 302.C140
56
BW 302.C180
72
BW 302.C230
94
■
Observe the floor area and minimum clearances
(see following chapter).
Preparing for installation
Transport and siting requirements
(cont.)
5787 232 GB
Installation