34
Plug
sXD
Terminals
Function
Explanation
223.1
223.2
U
Central fault message
Floating contact:
■
Closed: Fault
■
Open: No fault
■
Not suitable for safety LV
Connection values (contact rating):
■
Voltage: 230 V~
■
Max. switching current: 4(2) A
Central fault message
223.1
L1
230V~, 0.5 A
N
223.2
A
Fig. 27
A
Terminals on extension PCB
Plug
sXF
Terminals
Function
Explanation
224.2
2.
Primary pump for heat pump stage 2
Connection values
■
Output: 200 W
■
Voltage: 230 V~
■
Max. switching current: 4(2) A
224.3
2.
Secondary pump for heat pump
stage 2
Connection values
■
Output: 130 W
■
Voltage: 230 V~
■
Max. switching current: 4(2) A
224.4
r
2.
Switching an instantaneous heating
water heater, stage 2
Connection values
■
Output: 10 W
■
Voltage: 230 V~
■
Max. switching current: 4(2) A
224.5
2.
Circulation pump for cylinder heating
for heat pump stage 2
Connection values
■
Output: 130 W
■
Voltage: 230 V~
■
Max. switching current: 4(2) A
224.6
Connect cylinder loading pump and 2-way shut-off
valve in parallel.
Connection values
■
Output: 130 W
■
Voltage: 230 V~
■
Max. switching current: 4(2) A
Cylinder loading pump (DHW side)
M
2-way shut-off valve
Installation sequence
Electrical connection
(cont.)
5516461
Installation
Summary of Contents for BW 301.B06
Page 69: ...69 Fig 49 Maintenance Opening the casing door 5516461 Maintenance...
Page 76: ...76 Maintenance Condensation and moisture in the heat pump cont 5516461 Maintenance...
Page 79: ...79 Parts lists type BWC 301 B Parts not shown type BWC 301 B cont 5516461 Components...
Page 88: ...88 Parts lists type BWC 301 B Hydraulics type BWC 301 B cont 5516461 Components...
Page 91: ...91 Parts lists type BW 301 B Parts not shown type BW 301 B cont 5516461 Components...
Page 100: ...100 Parts lists type BW 301 B Hydraulics type BW 301 B cont 5516461 Components...
Page 103: ...103 Parts lists type BWS 301 B Parts not shown type BWS 301 B cont 5516461 Components...