Cascade via LON
Parameter
Setting
Lead appliance
Lag heat pump
"System definition"
Ó
"System scheme 7000"
"0"
to
"10"
"11"
"System definition"
Ó
"Cascade control 700A"
"2"
"0"
"System definition"
Ó
"Number of lag heat pumps in
cascade 5735"
"1"
to
"4"
–
"System definition"
Ó
"Output lag heat pump 700B"
"0"
to
"255"
–
"System definition"
Ó
"Use of heat pump in a cas-
cade 700C"
"0"
to
"31"
"0"
to
"31"
"System definition"
Ó
"Flow temperature for external
demand 730C"
–
"0"
to
"700"
(
≙
0 to
70 °C)
"Communication"
Ó
"Heat pump number in cas-
cade (LON) 5707"
–
"1"
to
"4"
(unique)
"Communication"
Ó
"Enable LON communication
module 7710"
–
"1"
"Communication"
Ó
"LON subscriber number
7777"
"1"
to
"99"
(unique)
"1"
to
"99"
(unique)
"Communication"
Ó
"LON system number 7798"
"1"
to
"5"
"1"
to
"5"
(as per lead
appliance)
"Communication"
Ó
"LON fault manager 7779"
"1"
to
"99"
(unique)
"1"
to
"99"
(unique)
The
additional
parameters for the heat
pump cascade are set during commis-
sioning by the certified heat pump con-
tractor.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)