9
Use a connection set or connection kit, available as an
accessory, to make the connection on the gas and
water sides.
Fitting accessories
Fit all accessories that are installed at the back of the
boiler (e.g. connection sets).
Preparing connections on site:
Connection set installation instructions
or
Assembly kit installation instructions
Note
Fit safety equipment in accordance with the national
regulations.
!
Please note
Avoid damaging the appliance.
Connect all pipework free of load and torque
stress.
The following diagram shows sample connection sets
for installation on finished walls, with connection to the
top or side.
100
569
46
40
50
c d
e f
g h
k
l m n p
a
b
140
50
320
361
398
410
80
A
C
D
F
E
B
E
F
B
A
D
C
K
G
H
G
Ø 60,5
+0,8
Ø 96
-0,5
Fig. 1
q
50
595
50
600
55
220
330
G
C
A
B
F
D
E
Fig. 2
A
Heating flow R
¾
B
DHW R
½
C
Gas connection R
¾
D
Cold water R
½
E
Heating return R
¾
F
DHW circulation R
½
(separate accessory)
G
Condensate drain facing backwards into the wall
H
Condensate drain to the side
K
Wiring area
Rated heating output
13, 19, 26
kW
35 kW
a (mm)
745
945
b (mm)
750
950
c (mm)
972
1172
d (mm)
1027
1227
e (mm)
1082
1302
f (mm)
1137
1337
g (mm)
1191
1391
h (mm)
1247
1447
k (mm)
1302
1562
l (mm)
1437
1637
m (mm)
1466
1666
n (mm)
1465
1665
p (mm)
1526
1726
q (mm)
201
224
Note
All height dimensions have a tolerance of +7 mm on
account of the adjustable feet.
Preparing for installation
Preparing for boiler installation
5789 302 GB
Installation
Summary of Contents for B2TB
Page 6: ...6 15 Keyword index 152 Index Index cont 5789 302 GB ...
Page 117: ...117 Parts lists Hydraulics 5789 302 GB Components ...
Page 154: ...154 5789 302 GB ...
Page 155: ...155 5789 302 GB ...