Setting the time and date - only for weather-compensated control units
The time and date need to be reset during commis-
sioning or after a prolonged time out of use (approx. 18
days).
Extended menu:
1.
å
2.
"Settings"
3.
"Time / Date"
4. Set current time and date.
Note on automatic testing of the flue gas temperature sensor
Weather-compensated control unit
Constant temperature control unit
As soon as the time and date have been set, the con-
trol unit automatically checks the function of the flue
gas temperature sensor.
The display shows:
"Flue gas temp sensor test"
and
"Active"
.
Note
If the flue gas temperature sensor is incorrectly posi-
tioned, commissioning is aborted and fault message A3
is shown (see page 95).
Immediately after being switched on, the control unit au-
tomatically checks the function of the flue gas tempera-
ture sensor.
The display shows:
"A"
.
Note
If the flue gas temperature sensor is incorrectly posi-
tioned, commissioning is aborted and fault message A3
is shown (see page 95).
Commissioning, inspection, maintenance
Selecting the language - only for…
(cont.)
5773 216 GB
Summary of Contents for B2TA
Page 101: ...101 Parts lists Overview of assemblies 5773 216 GB Components ...
Page 107: ...107 Parts lists Hydraulics 5773 216 GB Components ...
Page 118: ...118 0004 0002 0005 0006 0001 0003 Fig 77 Parts lists Miscellaneous 5773 216 GB Components ...
Page 142: ...142 5773 216 GB ...
Page 143: ...143 5773 216 GB ...