26
See page 12
Checking the power supply
Filling the heating system
Fill water
!
Please note
Unsuitable fill water increases the level of
deposits and corrosion and may lead to appli-
ance damage.
■
Flush the heating system thoroughly before
filling.
■
Only use fill water of potable water quality.
■
Antifreeze suitable for heating systems can be
added to the fill water. The antifreeze manu-
facturer must verify its suitability.
■
Fill and top-up water with a water hardness in
excess of the following values must be soft-
ened, e.g. with a small softening system for
heating water.
Total permissible hardness of the fill and top-up water
Total heating output
Specific system volume
kW
< 20 l/kW
≥
20 l/kW to < 50 l/kW
≥
50 l/kW
≤
50
≤
3.0 mol/m
3
(16.8 °dH)
≤
2.0 mol/m
3
(11.2 °dH)
< 0.02 mol/m
3
(0.11 °dH)
>
50 to
≤
200
≤
2.0 mol/m
3
(11.2 °dH)
≤
1.5 mol/m
3
(8.4 °dH)
< 0.02 mol/m
3
(0.11 °dH)
>
200 to
≤
600
≤
1.5 mol/m
3
(8.4 °dH)
≤
0.02 mol/m
3
(0.11 °dH)
< 0.02 mol/m
3
(0.11 °dH)
>
600
< 0.02 mol/m
3
(0.11 °dH)
< 0.02 mol/m
3
(0.11 °dH)
< 0.02 mol/m
3
(0.11 °dH)
A
B
Fig. 17
Shown with connection set for finished walls
(accessories)
1.
Check the pre-charge pressure of the diaphragm
expansion vessel (see page 43).
2.
Close the gas shut-off valve.
3.
Open shut-off valves
B
on the heating water side.
Commissioning, inspection, maintenance
Removing the front panels
5773 216 GB
Summary of Contents for B2TA
Page 101: ...101 Parts lists Overview of assemblies 5773 216 GB Components ...
Page 107: ...107 Parts lists Hydraulics 5773 216 GB Components ...
Page 118: ...118 0004 0002 0005 0006 0001 0003 Fig 77 Parts lists Miscellaneous 5773 216 GB Components ...
Page 142: ...142 5773 216 GB ...
Page 143: ...143 5773 216 GB ...