83
External functions
Parameter
Setting
External blocking of compres-
sor and pumps
"System definition"
Ó
"Effect of external block-
ing on pumps/compressor
701A"
"0"
to
"31"
External blocking of the com-
pressor; mixer in control
mode or CLOSED
"System definition"
Ó
"Effect of ext. blocking on
heat pump/heating circuits
7015"
"0"
to
"8"
"System definition"
Ó
"Effect of external block-
ing on pumps/compressor
701A"
"0"
to
"31"
Cooling function
Cooling function parameters
Setting
"Cooling"
Ó
"Cooling function 7100"
"3"
"Cooling"
Ó
"Cooling circuit 7101"
■
"1"
(heating circuit A1/HC1)
■
"2"
(heating circuit M2/HC2)
■
"4"
(separate cooling circuit
SKK)
Instantaneous heating water heater
Parameters for
Instantaneous heating water heater
Setting
"Electr booster heater"
Ó
"Enable instantaneous heating water heater
7900"
"1"
"Electr booster heater"
Ó
if applicable
"Enable instant. heating water heater for cen-
tral heating 7902"
"1"
"Electr booster heater"
Ó
"Output for instant. heating water heater at
power-OFF 790A"
■
"1"
for 3 kW
■
"2"
for 6 kW
■
"3"
for 9 kW
"DHW"
Ó
if applicable
"Enable electric heaters for DHW heating
6015"
"1"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5782 201 GB
Service