61
Required heat pump parameters
"Output compressor stage 5030"
During commissioning, the heating output of the heat
pump
must
be set subject to type.
Type AWT/AWT-AC
221.A04
221.A05
221.A07
221.A10
221.B10
221.A13
221.B13
221.B16
"Output compressor stage 5030"
4 kW
5 kW
7 kW
10 kW
13 kW
16 kW
Required parameters for components connected on site
Parameters may need to be set subject to the type of
appliance, the selected system scheme and the acces-
sories used.
Overview of required parameters: see the following
chapter.
Detailed explanations of parameters
"Vitotronic 200" service instructions
System scheme
Overview of all available system schemes
Component
System scheme
0
1
2
3
4
5
6
11
Heating circuit
A1/HC1
—
X
X
—
—
X
X
—
M2/HC2
—
—
—
X
X
X
X
—
DHW cylinder
X
—
X
—
X
—
X
—
Heating water buffer cylinder
—
0
0
X
X
X
X
—
Instantaneous heating water heater
X
X
X
X
X
X
X
—
Swimming pool
—
0
0
0
0
0
0
—
Cooling circuit
(Type AWT-AC only)
A1/HC1
—
0
0
—
—
0
0
—
M2/HC2
—
—
—
0
0
0
0
—
Separate cooling circuit
SKK
0
0
0
0
0
0
0
—
Electricity meter, 3-phase
0
0
0
0
0
0
0
0
Ventilation unit
0
0
0
0
0
0
0
0
X Component is selected.
0
Component may be added.
"Heat pump system examples"
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5776 028 GB
Summary of Contents for AWT 221.A04
Page 77: ...77 Maintenance Checking the fuses cont 5776 028 GB Maintenance...
Page 87: ...87 Indoor unit parts lists Indoor unit hydraulics cont 5776 028 GB Components...
Page 90: ...90 Indoor unit parts lists Indoor unit cylinder cont 5776 028 GB Components...
Page 137: ...137 Wind direction 11 Wind loads 11 Keyword index Keyword index cont 5776 028 GB...
Page 138: ...138 5776 028 GB...
Page 139: ...139 5776 028 GB...